ACS 600 MultiDrive – Technical Data
ACS 600 MultiDrive
A-35
Application Programs
Various application programs are available for the ACS 600 frequency
converters. Not all selections are available for all types. One
application program at a time can be loaded in the memory of the
frequency converter.
Digital Inputs
ACS/ACP 600, ACS 600 MultiDrive: Six Programmable Digital Inputs (Common
Ground):
24 VDC, -15 to +20 %
ACC 600: Six Digital Inputs (Common Ground):
24 VDC, -15 to +20 %
Logical Thresholds:
< 8 VDC
“0”, > 12 VDC
“1”
Input Current:
DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering Time Constant:
1 ms
Thermistor Input:
5 mA, < 1.5 k
W
“1” (normal temperature), > 4 k
W
“0” (high
temperature), Open Circuit
“0” (high temperature)
Internal Supply For Digital Inputs (+24 VDC):
Short circuit proof, group isolated
Isolation Test Voltage:
500 VAC, 1 minute
Input Updating Time:
12 ms (ACS 600), 44 ms (ACC 600), 4 ms (ACP 600), 10 ms
(ACS 600 MultiDrive)
An external 24 VDC supply can be used instead of the internal supply.
Digital Outputs
-
Relay Outputs
Three Programmable Relay Outputs
Switching Capacity:
8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Maximum Continuous Current:
2 A rms
Contact Material:
Silver Cadmium Oxide (AgCdO)
Isolation Test Voltage:
4 kVAC, 1 minute
Output Updating Time:
100 ms (ACS 600), 44 ms (ACC 600), 8 ms (ACP 600),
10 ms (ACS 600 MultiDrive)
DDCS Fibre Optic Link
Protocol:
DDCS (ABB Distributed Drives Communication System)
Encoder Input
ACS 600 Application Programs
Standard
CraneDrive
MotionControl
System
ACS/ACC/ACP 600, ACS 600 MultiDrive
NIOC-01 Board