Safety Instructions
10
ACS 600 MultiDrive
* manufactured before 1992
Man
u
factu
rer
Motor Type
Nominal Mains
Voltage
Requirement for
Motor
Insulation
System
ACS 600 du/dt Filter, ACS 600 Common Mode Filter and Insulated N-
bearing
P
N
< 100 kW
and
Frame Size < IEC 315
100 kW <
P
N
< 350 kW
or
Frame Size > IEC 315
P
N
> 350 kW
A
B
B
Random-
wound
M2_ and M3_
U
N
< 500 V
Standard
-
+ N
+ N + CMF
500 V <
U
N
< 600 V
Standard
+ du/dt
+ du/dt
+ du/dt + N + LCMF
or
Reinforced
-
+ N
+ N + CMF
600 V <
U
N
< 690 V
Reinforced
+ du/dt
+ du/dt
+ du/dt + N + LCMF
Form-wound
HXR and AM_
380 V <
U
N
< 690 V
Standard
n.a.
+ N + CMF
+ N + CMF
Old* form-
wound HX_
and modular
380 V <
U
N
< 690 V
Check from
the motor
manufacturer.
+ du/dt filter with voltages over 500 V + N + CMF
Random-
wound HXR
380 V <
U
N
< 690 V
Check from
the motor
manufacturer.
+ du/dt filter with voltages over 500 V + N + CMF
N
O
N
-
A
B
B
Random-
wound
U
N
< 420 V
Standard:
Û
LL
= 1300 V
-
+ N or CMF
+ N + CMF
420 V <
U
N
< 500 V
Standard:
Û
LL
= 1300 V
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1600 V,
0.2
microsecond
rise time
-
+ N or CMF
+ N + CMF
500 V <
U
N
< 600 V
Reinforced:
Û
LL
= 1600 V
+ du/dt
+ du/dt
+ du/dt + N + LCMF
or
Reinforced:
Û
LL
= 1800 V
-
+ N or CMF
+ N + CMF
600 V <
U
N
< 690 V
Reinforced:
Û
LL
= 1800 V
+ du/dt
+ du/dt
+ du/dt + N + LCMF
Form-wound
U
N
< 690 V
Reinforced:
Û
LL
= 2000 V,
0.3
microsecond
rise time
n.a.
+ N + CMF
+ N + CMF
Summary of Contents for ACS 600 MultiDrive
Page 4: ......
Page 7: ...ACS 600 MultiDrive v Applicable Standards B 2 Materials B 2 Other Technical Data B 2...
Page 8: ...vi ACS 600 MultiDrive...
Page 24: ...Safety Instructions 16 ACS 600 MultiDrive...
Page 69: ......