36
Group 13: Analogue Inputs
Code Description
1301
MINIMUM AI1
Relative minimum value of AI1 (%). Value corresponds to minimum reference
set by parameter 1104
EXT
REF
1
MIN
or 1107
EXT
REF
2
MIN
.
See Figure 3 on page 34.
1302
MAXIMUM AI1
Maximum value of AI1 (%). Value corresponds to maximum reference set by
parameter 1105
EXT
REF
1
MAX
or 1108
EXT
REF
2
MAX
.
See Figure 3 on page 34.
1303
FILTER AI1
Filter time constant for analogue input AI1. As the analogue input value
changes, 63 % of the change takes place within the time specified by this
parameter.
Note! Even if you select 0 s for the filter time constant, the signal is still filtered
with a time constant of 0.1 ms due to the signal interface hardware. This cannot
be changed by any parameters.
Figure 4 Filter time constant for analogue input AI1.
1304
MINIMUM AI2
Minimum value of AI2 (%). Value corresponds to minimum reference set by
parameter 1104
EXT
REF
1
MIN
or 1107
EXT
REF
2
MIN
.
1305
MAXIMUM AI2
Maximum value of AI2 (%). Value corresponds to maximum reference set by
parameter 1105
EXT
REF
1
MAX
or 1108
EXT
REF
2
MAX
.
1306
FILTER AI2
Filter time constant for AI2. Refer to parameter 1303
FILTER
AI
1.
63
[%]
100
Time constant
t
Filtered Signal
Unfiltered Signal