Application Macro Factory (1)
This macro is intended for applications where there is no control panel
available. It provides a general purpose I/O configuration that is typically used
in North America.
The value of parameter 9902 is 0. DI 4 is connected.
*Note! DI 4 is used to configure ACS 140. It is read only once when power is
connected. When DI 4 is connected (1) the following applies:
•
Motor nominal values are 230/400 V and 60 Hz and 1720 rpm.
•
Input and output signals are scaled according to 60 Hz.
•
Maximum frequency is 60 Hz.
Note! Stop signal disabled: panel START/STOP button interlocked (local).
Factory (1) parameter values:
Input signals
Output signals
U/I jumper S1
• Start, stop and direction (DI1,2,3) • An. output AO: Frequency
• Analogue reference (AI1)
• Relay output 1: Fault
• Ramp pair 1/2 selection (DI5)
• Relay output 2: Running
9905
MOTOR
NOM
VOLT
230/480
V
1105
EXT
REF
1
MAX
60 Hz
9907
MOTOR
NOM
FREQ
60
Hz
1106
EXT
REF
2
SELECT
0 (
KEYPAD
)
9908
MOTOR
NOM
SPEED
1720 rpm
1201
CONST
SPEED
SEL
0 (
NOT
SEL
)
1001
EXT
1
COMMANDS
4 (
DI
1
P
,2
P
,
P
)
1503
AO
CONTENT
MAX
60 Hz
1002
EXT
2
COMMANDS
0 (
NOT
SEL
)
1601
RUN
ENABLE
0 (
NOT
SEL
)
1003
DIRECTION
3 (
REQUEST
)
2008
MAXIMUM
FREQ
60 Hz
1101
KEYPAD
REF
SEL
1 (
REF
1)
2105
PREMAGN
SEL
0 (
NOT
SEL
)
1102
EXT
1/
EXT
2
SEL
6 (
EXT
1)
2201
ACC
/
DEC
1/2
SEL
5 (
DI
5)
1103
EXT
REF
1
SELECT
1 (
AI
1)
S1:1:U
Control
Terminals
Function
1
SCR
2
AI 1
External reference1; 0...10 V <=> 0...60 Hz
3
AGND
4
10 V
Reference voltage 10 VDC
5
AI 2
Not used
6
AGND
7
AO
Output frequency 0...20 mA <=> 0...60 Hz
8
AGND
9
+12 V
+12 VDC
10 DCOM
11 DI 1
Momentary activation with DI2 activated: Start
12 DI 2
Momentary deactivation: Stop
13 DI 3
Fwd/Rev; Activate to reverse rotation direction
14 DI 4
Has to be connected!*
15 DI 5
Ramp pair selection. Activate to select ramp pair 2.
Defaults: 5 s (ramp pair 1), 60 s (ramp pair 2)
16 DO 1A
Relay output 1
Fault: open
17 DO 1B
18 DO 2A
Relay output 2
Running: closed
19 DO 2B
mA