16
Application Macro ABB Standard
This general purpose macro is typically used in Europe. It gives two more
preset speeds compared to Factory Macro (0).
The value of parameter 9902 is 1.
*Constant speed selection: 0 = open, 1 = connected
ABB Standard parameter values:
Input signals
Output signals
U/I jumper S1
• Start, stop and direction (DI1,2)
• An. output AO: Frequency
• Analogue reference (AI1)
• Relay output 1: Fault
• Preset speed selection (DI3,4)
• Relay output 2: Running
• Ramp pair 1/2 selection (DI5)
DI3
DI4
Output
0
0
Reference through AI1
1
0
Const speed 1 (1202)
0
1
Const speed 2 (1203)
1
1
Const speed 3 (1204)
9905
MOTOR
NOM
VOLT
230/400 V
1105
EXT
REF
1
MAX
50 Hz
9907
MOTOR
NOM
FREQ
50
Hz
1106
EXT
REF
2
SELECT
0 (
KEYPAD
)
9908
MOTOR
NOM
SPEED
1440 rpm
1201
CONST
SPEED
SEL
7 (
DI
3,4)
1001
EXT
1
COMMANDS
2 (
DI
1,2)
1503
AO
CONTENT
MAX
50 Hz
1002
EXT
2
COMMANDS
0 (
NOT
SEL
)
1601
RUN
ENABLE
0 (
NOT
SEL
)
1003
DIRECTION
3
(
REQUEST
)
2008
MAXIMUM
FREQ
50 Hz
1101
KEYPAD
REF
SEL
1 (
REF
1)
2105
PREMAGN
SEL
0 (
NOT
SEL
)
1102
EXT
1/
EXT
2
SEL
6 (
EXT
1)
2201
ACC
/
DEC
1/2
SEL
5 (DI5)
1103
EXT
REF
1
SELECT
1 (
AI
1)
S1:1:U
Control
Terminals
Function
1
SCR
2
AI 1
External reference1; 0...10 V <=> 0...50 Hz
3
AGND
4
10 V
Reference voltage 10 VDC
5
AI 2
Not used
6
AGND
7
AO
Output frequency 0...20 mA <=> 0...50 Hz
8
AGND
9
+12 V
+12 VDC
10 DCOM
11 DI 1
Start/Stop: Activate to start
12 DI 2
Fwd/Rev: Activate to reverse rotation direction
13 DI 3
Constant speed selection*
14 DI 4
Constant speed selection*
15 DI 5
Ramp pair selection. Activate to select ramp
pair 2. Defaults: 5 s / 60 s (ramp pair 1/2)
16 DO 1A
Relay output 1
Fault: open
17 DO 1B
18 DO 2A
Relay output 2
Running: closed
19 DO 2B
mA