ACS 140 Complete Parameter List
Initially, only the so called basic parameters (shaded grey in Table 3) are
visible. The menu function -LG- is used to make the full parameter set visible.
S = Parameters can be modified only when the drive is stopped.
M = Default value depends on the selected macro (*).
Table 3 Full parameter set.
Code Name
Range
Resolution Default
User
S
M
Group 99
START-UP DATA
9902
APPLIC
MACRO
0-7
1
0 (
FACTORY
)
ä
9905
MOTOR
NOM
VOLT
200, 208,220,
230, 240,380,
400, 415,440,
460, 480 V
-
*
ä ä
9906
MOTOR
NOM
CURR
0.5*I
N
- 1.5*I
N
0.1 A
I
N
ä
9907
MOTOR
NOM
FREQ
0-250 Hz
1 Hz
*
ä ä
9908
MOTOR
NOM
SPEED
0-3600 rpm
1 rpm
*
ä ä
Group 01
OPERATING DATA
0102
SPEED
0-9999 rpm
1 rpm
-
0103
OUTPUT
FREQ
0-250 Hz
0.1 Hz
-
0104
CURRENT
-
0.1 A
-
0106
POWER
-
0.1 kW
-
0107
DC
BUS
VOLTAGE
0-999.9 V
0.1 V
-
0109
OUTPUT
VOLTAGE
0-480 V
0.1 V
-
0110
ACS
140
TEMP
0-150
°
C
0.1
°
C
-
0111
EXT
REF
1
0-250 Hz
0.1 Hz
-
0112
EXT
REF
2
0-100 %
0.1 %
-
0113
CTRL
LOCATION
0-2
1
-
0114
RUN
TIME
0-99.99 kh
0.01 kh
-
0115
kWh
COUNTER
0-9999 kWh
1 kWh
-
0116
APPL
BLK
OUTPUT
0-100 %
0.1 %
-
0117
DI
1-
DI
4
STATUS
0000-1111
-
0118
AI
1
0-100 %
0.1 %
-
0119
AI2
0-100 %
0.1 %
-
0121
DI
5 &
RELAYS
0000-0111
-
0122
AO
0-20 mA
0.1 mA
-
0124
ACTUAL
VALUE
1
0-100 %
0.1 %
-
0125
ACTUAL
VALUE
2
0-100 %
0.1 %
-
0126
CONTROL
DEV
-100-100 %
0.1 %
-
0128
LAST
FAULT
0-22
1
0
-
0129
PREVIOUS
FAULT
0-22
1
0
-
0130
OLDEST
FAULT
0-22
1
0
-
Group 10
COMMAND INPUTS
1001
EXT
1
COMMANDS
0-10
1
*
ä ä
1002
EXT
2
COMMANDS
0-10
1
*
ä ä
1003
DIRECTION
1-3
1
*
ä ä