18
Application Macro Alternate
This macro offers an I/O configuration that is adopted to a sequence of DI
control signals used when alternating the direction of rotation of the drive.
The value of parameter 9902 is 3.
*Constant speed selection: 0 = open, 1 = connected
Application macro Alternate parameter values:
Input signals
Output signals
U/I jumper S1
• Start, stop and direction (DI1,2)
• An. output AO: Frequency
• Analogue reference (AI1)
• Relay output 1: Fault
• Preset speed selection (DI3,4)
• Relay output 2: Running
• Ramp pair 1/2 selection (DI5)
DI3
DI4
Output
0
0
Reference through AI1
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
9905
MOTOR
NOM
VOLT
230/400 V
1105
EXT
REF
1
MAX
50 Hz
9907
MOTOR
NOM
FREQ
50
Hz
1106
EXT
REF
2
SELECT
0 (
KEYPAD
)
9908
MOTOR
NOM
SPEED
1440 rpm
1201
CONST
SPEED
SEL
7 (
DI
3,4)
1001
EXT
1
COMMANDS
9 (
DI
1
F
,2
R
)
1503
AO
CONTENT
MAX
50 Hz
1002
EXT
2
COMMANDS
0 (
NOT
SEL
)
1601
RUN
ENABLE
0 (
NOT
SEL
)
1003
DIRECTION
3 (
REQUEST
)
2008
MAXIMUM
FREQ
50 Hz
1101
KEYPAD
REF
SEL
1 (
REF
1)
2105
PREMAGN
SEL
0 (
NOT
SEL
)
1102
EXT
1/
EXT
2
SEL
6 (
EXT
1)
2201
ACC
/
DEC
1/2
SEL
5 (
DI
5)
1103
EXT
REF
1
SELECT
1 (
AI
1)
S1:1:U
Control
Terminals
Function
1
SCR
2
AI 1
External reference1; 0...10 V <=> 0...50 Hz
3
AGND
4
10 V
Reference voltage 10 VDC
5
AI 2
Not used
6
AGND
7
AO
Output frequency 0...20 mA <=> 0...50 Hz
8
AGND
9
+12 V
+12 VDC
10 DCOM
11
DI 1
Start fwd; If DI1 state is the same as DI2, drive stops
12 DI 2
Start reverse
13 DI 3
Constant speed select*
14 DI 4
Constant speed select*
15 DI 5
Ramp pair selection. Activate to select ramp
pair 2. Defaults: 5 s / 60 s (ramp pair 1/2)
16 DO 1A
Relay output 1
Fault: open
17 DO 1B
18 DO 2A
Relay output 2
Running: closed
19 DO 2B
mA