Electrical installation 85
Safe torque off (XSTO)
For the drive to start, both connections (OUT1 to IN1, and OUT2 to IN2) must be closed.
By default, the terminal block has jumpers to close the circuit. Remove the jumpers before
connecting an external Safe torque off circuitry to the drive. See page
Control cable connection procedure
See the cable routing on page
and connect the control cables as follows:
1. Ground the shields of all control cables connected to the control unit at the clamp
plate. The shields should be continuous as close to the terminals of the control unit as
possible. Only remove the outer jacket of the cable at the cable clamp so that the
clamp presses on the bare shield.
2. Connect the conductors to the appropriate detachable terminals (see page
of the
control unit. At the terminal block, use shrink tubing or insulating tape to contain any
stray strands. The shield (especially in case of multiple shields) can also be
terminated with a lug and fastened with a screw at the clamp plate. Leave the other
end of the shield unconnected or ground it indirectly via a few nanofarads high-
frequency capacitor eg, 3.3 nF / 630 V. The shield can also be grounded directly at
both ends if they are
in the same ground line
with no significant voltage drop between
the end points.Tighten the screws to secure the connection.
Note:
Keep any signal wire pairs twisted as close to the terminals as possible.
Twisting the wire with its return wire reduces disturbances caused by inductive
coupling.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...