![ABB ACQ810 Hardware Manual Download Page 109](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066109.webp)
Technical data 109
Fuse tables
gG fuses
Drive type
ACq810-04…
Input
current
Min.
short-
circuit
current
1)
Fuse
A
A
A
A
2
s
V
Manufacturer
Type
IEC
size
-302A-4
297
8280
500
2 900 000 500
ABB Control OFAF3H500
3
-361A-4
355
8280
500
2 900 000 500
ABB Control OFAF3H500
3
-414A-4
407
8280
500
2 900 000 500
ABB Control OFAF3H500
3
-477A-4
459
10200
630
4 000 000 500
ABB Control OFAF3H630
3
-550A-4
531
10200
630
4 000 000 500
ABB Control OFAF3H630
3
-616A-4
599
13500
800
7 400 000 500
ABB Control OFAF3H800
3
-704A-4
689
13500
800
7 400 000 500
ABB Control OFAF3H800
3
1)
minimum short-circuit current of the installation
Note 1:
See also
Implementing thermal overload and short-circuit protection
on page
. For UL recognized
on page
.
Note 2:
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Larger fuses than the recommended ones must not be used.
Note 4:
Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
00581898, 00581898
Ultrarapid (aR) fuses
Drive type
ACS800-04…
Input
current
A
Min.
short-
circuit
current
1)
Fuse
A
A
A
2
s
V
Manufacturer
Type DIN
43620
Size
-302A-4
297
4000
800
465 000
690
Bussmann
170M6812
DIN2*
-361A-4
355
4000
800
465 000
690
Bussmann
170M6812
DIN2*
-414A-4
407
4000
800
465 000
690
Bussmann
170M6812
DIN2*
-477A-4
459
7800
1250
1 950 000
690
Bussmann
170M8554
DIN3
-550A-4
531
7800
1250
1 950 000
690
Bussmann
170M8554
DIN3
-616A-4
599
8850
1400
3 900 000
690
Bussmann
170M8555
DIN3
-704A-4
689
8850
1400
3 900 000
690
Bussmann
170M8555
DIN3
1)
minimum short-circuit current of the installation
Note 1:
Implementing thermal overload and short-circuit protection
on page
. For UL recognized
fuses, see
Note 2:
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Larger fuses than the recommended ones must not be used.
Note 4:
Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
00581898, 00581898
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...