76 Electrical installation
•
or by twisting the shield as follows: flattened width > 1/5 · length.
DC connection
The UDC+ and UDC– terminals are intended for common DC configurations of a number
of drives, allowing regenerative energy from one drive to be utilized by the other drives in
motoring mode. Contact your local ABB representative for further instructions.
Checking the settings of the cooling fan transformer
The voltage transformer of the cooling fan is located at the top right-hand corner of the
drive module. Remove the front cover for adjusting the settings and replace the cover after
setting.
a
b
b > 1/5 · a
Set according to the supply voltage range:
380 V, 400 V, 415 V, 440 V or 480 V
Set to 220 V if the supply frequency is 60 Hz. Set to
230 V if the supply frequency is 50 Hz.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...