40 Planning the cabinet installation
Free space at top with high air inlet gratings in the cabinet door
The required free space at the top of the module is shown below when the air inlet gratings
in the cabinet door are as high as the grating of the module. See also page
.
Free space at top with low air inlet gratings in the cabinet door
The required free space at the top of the module is shown below when the air inlet gratings
are located only in the lower part of the cabinet door.
Note:
Air inlet gratings only at the
lower part of the cabinet door are not recommended without an extra fan. The air baffles
are examples. See also page
300 mm
200 mm
(11.81 in.)
(7.87 in.)
Air baffles
not required if the
drive module
touches the
cabinet door
Air outlet in the cabinet
door
Air outlet on the
cabinet roof
200 mm
(7.87 in.)
Air outlet in the cabinet
door
300 mm
(11.81 in.)
Air baffles
Air outlet on the cabinet
roof
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...