![ABB ACQ810 Hardware Manual Download Page 41](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066041.webp)
Planning the cabinet installation 41
Free space at the side and front of the drive module
The figure below shows the required free space in a unit with motor busbars connected to
the left-hand side of the module. The required free space when no vertical busbars are
used is also shown.
1)
When cables are connected to the output busbars of the pedestal 100 mm (3.94 in.) free space around
the busbars is required for cooling.
2)
When cables connected to the vertical output busbar terminals 50 mm (1.97 in.) free space around the
busbar terminals is required for cooling.
3)
The required free space in front of the unit depends on the gratings in the cabinet door:
• 0 mm (0 in.) with air inlets as high as the grating in the module 1120 mm (44 in.)
• 150 mm (5.91 in.) with air inlets at the lower part of the cabinet only.
4)
No extra space is needed at the back.
Other installation positions
Contact your local ABB representative.
0 mm
(0 in.)
150
mm (5.91
in
.)
100 mm (3.94 in.)
50 mm (1.97 in.)
Air inlet side
2)
1)
3)
3)
4)
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...