Electrical installation 81
Default I/O connection diagram
XPOW
External power input
24 V DC, 1.6 A
+24VI
1
GND
2
XRO1, XRO2
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
NO
1
COM
2
NC
3
Relay output RO2 [Fault(-1)]
250 V AC / 30 V DC
2 A
NO
4
COM
5
NC
6
XD24
+24 V DC*
+24VD
1
Digital input ground
DIGND
2
+24 V DC*
+24VD
3
Digital input/output ground
DIOGND
4
Ground selection jumper
AI1
XDI
Digital input DI1 [Stop/Start]
DI1
1
Digital input DI2 [Constant speed 1]
DI2
2
Digital input DI3 [Reset]
DI3
3
Digital input DI4
DI4
4
Digital input DI5 [EXT1/EXT2 selection]
DI5
5
Start interlock (0 = Stop)
DIIL
A
XDIO
Digital input/output DIO1 [Output: Ready]
DIO1
1
Digital input/output DIO2 [Output: Running]
DIO2
2
XAI
Reference voltage (+)
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analog input AI1 (Current or voltage, selectable by
jumper AI1) [Current] [Speed reference 1]
AI1+
4
AI1-
5
Analog input AI2 (Current or voltage, selectable by
jumper AI2) [Current] [Process actual value 1]
AI2+
6
AI2-
7
AI1 current/voltage selection jumper
AI1
AI2 current/voltage selection jumper
AI2
XAO
Analog output AO1 [Current]
AO1+
1
AO1-
2
Analog output AO2 [Speed rpm]
AO2+
3
AO2-
4
XD2D
Drive-to-drive link termination jumper
T
Drive-to-drive link.
B
1
A
2
BGND
3
XSTO
Safe Torque Off. Both circuits must be closed for the
drive to start.
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
Notes:
[…] denotes default setting with ACQ810
standard pump control program (
Factory
defs
macro). See
Firmware manual
for
other macros.
*Total maximum current: 200 mA
The wiring shown is for demonstrative
purposes only. Further information of the
usage of the connectors and jumpers are
given in the text; see also the chapter
.
Wire sizes and tightening torques:
XPOW, XRO1, XRO2, XD24:
0.5 … 2.5 mm
2
(24…12 AWG). Torque:
0.5 N·m (5 lbf·in)
XDI, XDIO, XAI, XAO, XD2D, XSTO:
0.5 … 1.5 mm
2
(28…14 AWG). Torque:
0.3 N·m (3 lbf·in)
XPOW
(2-pole, 2.5 mm
2
)
Order of terminal headers and
jumpers
XRO1
(3-pole, 2.5 mm
2
)
XRO2
(3-pole, 2.5 mm
2
)
XD24
(4-pole, 2.5 mm
2
)
XDI
(6-pole, 1.5 mm
2
)
DI/DIO grounding selection
XDIO
(2-pole, 1.5 mm
2
)
XAI
(7-pole, 1.5 mm
2
)
AI1, AI2
XAO
(4-pole, 1.5 mm
2
)
XD2D
(3-pole, 1.5 mm
2
)
XSTO (orange)
(4-pole, 1.5 mm
2
)
T
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...