68 Diagnostics
EN
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
7310
Overspeed
Motor is turning faster than highest
allowed speed.
Check the minimum/maximum speed
settings, parameters
,
motor braking torque, torque control,
brake chopper and resistor(s).
7510
FBA A communication
(Programmable fault:
Cyclical communication between
drive and fieldbus adapter module A
or between PLC and fieldbus adapter
module A is lost.
Check the status of fieldbus
communication. Check parameter
groups
,
and
. Check cable
connections and communication of
master.
8000
Unicos system error
System fault.
Power cycle.
8009
Current limit
Motor actual current exceeded the
limit defined in parameter
.
Reduce the motor load. Check
for any jam or stall in motor.
See parameter
.
80A0
AI supervision
An analog signal is outside the limits
specified for the analog input.
Check signal level, auxiliary code,
wiring connected to the input and the
minimum/maximum limits of the input
in parameter group
.
80B0
Signal supervision 1
Fault generated by the signal
supervision function 1.
Check the source of the fault
(parameter
80B1
Signal supervision 2
Fault generated by the signal
supervision function 2.
Check the source of the fault
(parameter
80B2
Signal supervision 3
Fault generated by the signal
supervision function 3.
Check the source of the fault
(parameter
80B3
Signal supervision 4
Fault generated by the signal
supervision function 4.
Check the source of the fault
(parameter
80B4
Signal supervision 5
Fault generated by the signal
supervision function 5.
Check the source of the fault
(parameter
80B5
Signal supervision 6
Fault generated by the signal
supervision function 6.
Check the source of the fault
(parameter
9081
External fault 1
Fault in external device 1.
Check external device and parameter
9082
External fault 2
Fault in external device 2.
Check external device and parameter
9083
External fault 3
Fault in external device 3.
Check external device and parameter
9084
External fault 4
Fault in external device 4.
Check external device and parameter
9085
External fault 5
Fault in external device 5.
Check external device and parameter
A2A1
Current calibration
Current offset and gain measurement
calibration will occur at next start.
Informative warning. (See parameter
Code
(hex)
Fault / Aux. code
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
1 – AI1LessMIN
3 – AI2LessMIN
2 – AI1GreaterMAX
4 – AI2GreaterMAX
ACQ80R0-R8 QIG.book Page 68 Friday, February 1, 2019 1:18 PM