Parameters List 39
EN
TR
ZH
32.49 Supervision 5 low
-21474836.00… 21474836.00 -
0.00
32.50 Supervision 5 high
-21474836.00… 21474836.00 -
0.00
32.51 Supervision 5 hysteresis
0.00...100000.00
-
0.00
32.55 Supervision 6 function
-
Disabled[0]
32.56 Supervision 6 action
No action[0], Warning[1],
Fault[2], Fault if running[3]
-
No action[0]
32.57 Supervision 6 signal
-
Zero[0]
32.58 Supervision 6 filter time
0.000...30.000
s
0.000
32.59 Supervision 6 low
-21474836.00… 21474836.00 -
0.00
32.60 Supervision 6 high
-21474836.00… 21474836.00 -
0.00
32.61 Supervision 6 hysteresis
0.00...100000.00
-
0.00
35 Motor thermal protection
35.01 Motor estimated temperature
-60…1000 °C
°C
0
35.02 Measured temperature 1
-60…5000 °C
°C
0
35.03 Measured temperature 2
-60…5000 °C
°C,
0
35.05 Motor overload level
0.0...300.0 %
%
0.0
35.11 Temperature 1 source
0, 1, 5...7, 11
-
Estimated
temperature
[1]
35.12 Temperature 1 fault limit
-60…5000 °C
°C
130 °C or 266
°F
35.13 Temperature 1 warning limit
-60…5000 °C
°C
110 °C
35.14 Temperature 1 AI source
0...2
-
Not
selected[0]
35.21 Temperature 2 source
-
Disabled[0]
35.22 Temperature 2 fault limit
-60…5000 °C
°C
130 °C
35.23 Temperature 2 warning limit
-60…5000 °C
°C
110 °C
35.24 Temperature 2 AI source
-
Not
selected[0]
35.50 Motor ambient temperature
-60…100 °C
°C
20
35.51 Motor load curve
50…150
%
100
35.52 Zero speed load
50…150
%
100
35.53 Break point
1.00 … 500.00
Hz
45.00
35.54 Motor nominal temperature rise
0…300 °C
°C
80
35.55 Motor thermal time constant
100…10000
s
256
35.56 Motor overload action
No action[0],Warning only[1],
Warning and fault[2]
-
Warning and
fault[2
35.57 Motor overload class
Class 5[0], Class 10[1], Class
20[2], Class 30,[3] Class 40[4]
-
Class 20[2]
Index
Name
Range/List
Unit
Default
Disabled[0]
2 × Pt100 analog I/O[6]
Estimated temperature[1]
3 × Pt100 analog I/O[7]
1 × Pt100 analog I/O[5]
Direct temperature[11]
Not selected[0]
AI1 actual value[1]
AI2 actual value[2]
Other...