Diagnostics 67
EN
TR
ZH
6684
EFB load fault
Embedded fieldbus (EFB) protocol
firmware could not be loaded.
Reload the firmware or replace the
unit. Contact ABB.
Version mismatch between EFB
protocol firmware and drive firmware.
6685
EFB fault 2
Fault reserved for the EFB protocol
application.
Check the documentation of the
protocol.
6686
EFB fault 3
6882
Text 32-bit table
overflow
Internal fault.
Reset fault. If fault persists, contact
ABB.
6885
Text file overflow
Internal fault.
The table size is too short for
opening language file.
Reset the fault. If fault persists,
contact ABB.
7081
Control panel loss
Control panel or PC tool ceased
communicating.
Check connections. Disconnect and
reconnect the control panel.
7085
Incompatible option
module
Fieldbus option module not
supported.
Replace the module with a supported
type.
7121
Motor stall
Motor is operating in stall region.
Check motor load, drive ratings and
fault function parameters.
7122
Motor overload
Motor current is too high.
Check for overloaded motor
Adjust the parameters used for the
motor overload function.
(
7181
Brake resistor
Brake resistor broken or not
connected.
Check connections and brake resistor
dimensioning.
7183
BR excess
temperature
Brake resistor temperature has
exceeded the limit.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings and fault limit
settings. Check braking cycle limits.
7184
Brake resistor wiring
Brake resistor short circuit or brake
chopper control fault.
Check connections.
7191
BC short circuit
Short circuit in brake chopper IGBT. Check the electrical specifications.
Replace brake chopper.
7192
BC IGBT excess temp Brake chopper IGBT temperature
exceeded internal fault limit.
Let chopper cool down. Check
ambient temperature, cooling fan, air
flow, resistor overload protection
function settings, braking cycle limits
and supply voltage.
71A3
Mech brake opening
failed
Mechanical brake control is faulty.
Brake open acknowledgment is not
matching the actual status.
Check connections, brake settings
and brake acknowledgment signal.
73B0
Emergency ramp failed Emergency stop did not finish within
expected time.
Check predefined ramp times
(
…
for mode Off1,
for mode Off3).
73F0
Overfrequency
Maximum allowed output frequency
exceeded.
Check the auxiliary code.
00FA Motor is turning faster than the
highest allowed frequency due to
incorrectly set minimum/maximum
frequency or the motor rushes
because of too high supply voltage or
incorrect supply voltage selection in
parameter
Check minimum/maximum frequency
settings, parameters
and
.
Check used supply voltage and
voltage selection parameter
.
Other -
Contact your local ABB
representative, quoting the auxiliary
code.
Code
(hex)
Fault / Aux. code
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do