Guidelines for planning the electrical installation 95
Conductor type, IEC and North America
The following table includes various conductor types that can be connected to the
drive. For optimal drive performance, VFD cable is preferred. When not available, see
the following standards in the footnotes below.
Power cable shield, IEC and North America
If the cable shield is used as the sole PE conductor, make sure that the conductivity
agrees with the PE conductor requirements. See section
, or IEC 61800-5-1.
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminum shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape or copper wire. The
better and tighter the shield, the lower the emission level and bearing currents.
Conductor type
Notes
1, 2)
Copper
Allowed
All frames
Aluminum (UL installations)
Not allowed
All frames
Aluminum (IEC installations)
Not allowed
Frames R1…R4
Allowed
Frames R5…R8 (for
U
N
=
230 V only)
1)
The selection of cable sizing/type is based on 70 (NEC) Table 310.15 (B) (16), formerly table
310.16, for copper wires is based on 75 °C (167 °F), and wire insulation at 30 °C (86 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable
or earth (directly buried). For other ambient temperatures addition derating may be required.
See 310.15(B)(2)(a) for the ampacity correction factors where the ambient temperature is
other than 30°C (86°F).
See to 310.15(B)(3)(a) for more than three current-carrying conductors.
For other conditions, size the cables according to local safety regulations, appropriate input
voltage and the load current of the drive. See also page 297 for the accepted cable sizes of
the drive
2)
Select cable size/type is based on CSA 22.1 latest acceptable revision for your area.
1
Insulation jacket
1
3
4
5
2
Summary of Contents for ACH580-01 Series
Page 1: ...ABB DRIVES FOR HVAC ACH580 01 drives 0 75 to 250 kW 1 to 350 hp Hardware manual...
Page 2: ...Related documents are listed on page 27...
Page 4: ......
Page 14: ...14 Table of contents...
Page 24: ...24 Safety instructions...
Page 34: ...34 Introduction to the manual...
Page 52: ...52 Operation principle and hardware description...
Page 112: ...112 Guidelines for planning the electrical installation...
Page 122: ...122 Electrical installation IEC IEC R6 R9 Screw A EMC DC B EMC AC C VAR 3 B 3 A 4 C...
Page 156: ...156 Electrical installation IEC IEC R4 0 5 0 6 N m 0 4 lbf ft 7 4 3 8 11 5 9 11 6 10 8 4...
Page 157: ...Electrical installation IEC 157 IEC R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 4 8...
Page 160: ...160 Electrical installation IEC IEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 210: ...210 Electrical installation North America UL NEC R4 4 lbf ft 7 4 3 11 5 9 11 6 10...
Page 211: ...Electrical installation North America 211 UL NEC 8 R5 4 6 11 11 10 3 5 7 9 0 4 lbf ft 4...
Page 214: ...214 Electrical installation North America UL NEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 222: ...222 Electrical installation North America UL NEC...
Page 242: ...242 Maintenance and hardware diagnostics...
Page 245: ...Technical data 245 See definitions and notes on page 247...
Page 308: ...308 Technical data...
Page 310: ...310 Dimension drawings Frame R1 IP21 UL Type 1 3AXD10000601652...
Page 311: ...Dimension drawings 311 Frame R1 IP55 UL Type 12 3AXD10000601699...
Page 312: ...312 Dimension drawings Frame R1 IP55 F278 UL Type 12 3AXD10000649451...
Page 313: ...Dimension drawings 313 Frame R2 IP21 UL Type 1 3AXD10000602398...
Page 314: ...314 Dimension drawings Frame R2 IP55 UL Type 12 3AXD10000602401...
Page 315: ...Dimension drawings 315 Frame R2 IP55 F278 UL Type 12 3AXD10000649654...
Page 316: ...316 Dimension drawings Frame R3 IP21 UL Type 1 3AXD10000602466...
Page 317: ...Dimension drawings 317 Frame R3 IP55 UL Type 12 3AXD10000602519...
Page 318: ...318 Dimension drawings Frame R3 IP55 E223 UL Type 12 3AXD10000649130...
Page 319: ...Dimension drawings 319 Frame R3 IP55 F278 F316 UL Type 12 3AXD10000649130...
Page 320: ...320 Dimension drawings Frame R4 IP21 UL Type 1 3AXD10000332430...
Page 321: ...Dimension drawings 321 Frame R4 IP55 UL Type 12 3AXD10000427933...
Page 322: ...322 Dimension drawings Frame R4 IP55 E223 UL Type 12 3AXD10000649283...
Page 323: ...Dimension drawings 323 Frame R4 IP55 F278 F316 UL Type 12 3AXD10000649283...
Page 324: ...324 Dimension drawings Frame R5 IP21 UL Type 1 3AXD10000412280...
Page 325: ...Dimension drawings 325 Frame R5 IP55 UL Type 12 3AXD10000415964...
Page 326: ...326 Dimension drawings Frame R5 IP55 E223 UL Type 12 3AXD10000687928...
Page 327: ...Dimension drawings 327 Frame R5 IP55 F278 F316 UL Type 12 3AXD10000687928...
Page 328: ...328 Dimension drawings Frame R6 IP21 UL Type 1 3AXD10000258705...
Page 329: ...Dimension drawings 329 Frame R6 IP55 UL Type 12 3AXD10000330667...
Page 330: ...330 Dimension drawings Frame R7 IP21 UL Type 1 3AXD10000258995...
Page 331: ...Dimension drawings 331 Frame R7 IP55 UL Type 12 3AXD10000330932...
Page 332: ...332 Dimension drawings Frame R8 IP21 UL Type 1 3AXD10000287670...
Page 333: ...Dimension drawings 333 Frame R8 IP55 UL Type 12 3AXD10000332446...
Page 334: ...334 Dimension drawings Frame R9 IP21 UL Type 1 3AXD10000287428...
Page 335: ...Dimension drawings 335 Frame R9 IP55 UL Type 12 3AXD10000334310...
Page 336: ...336 Dimension drawings...
Page 362: ...362 Safe torque off function...
Page 388: ...388 Optional I O extension modules...