262 Technical data
Fuses (IEC)
gG as well as uR or aR fuses for protection against short-circuit in the input power
cable or drive are listed below. Either fuse type can be used for frames R1…R9 if it
operates rapidly enough. The operating time depends on the supply network
impedance and the cross-sectional area and length of the supply cable.
Note 1:
Implementing short-circuit and thermal overload protection
on page
.
Note 2:
Fuses with higher current rating than the recommended ones must not be
used.
Note 3:
Fuses from other manufacturers can be used if they meet the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
gG fuses (IEC)
Check on the fuse time-current curve to ensure the operating time of the fuse is
below 0.5 seconds. Obey the local regulations.
Type
ACH580-01-
Min. short-
circuit
current
1)
Input
current
gG (IEC 60269)
Nominal
current
I
2
t
Voltage
rating
ABB type
IEC
60269
size
A
A
A
A
2
s
V
3-phase
U
N
= 230 V
04A7-2
200
4.7
25.0
2500.0
500
OFAF000H25
000
06A7-2
200
6.7
25.0
2500.0
500
OFAF000H25
000
07A6-2
200
7.6
25.0
2500.0
500
OFAF000H25
000
012A-2
200
12.0
25.0
2500.0
500
OFAF000H25
000
018A-2
200
16.9
25.0
2500.0
500
OFAF000H25
000
025A-2
320
24.5
40.0
7700.0
500
OFAF000H40
000
032A-2
320
31.2
40.0
7700.0
500
OFAF000H40
000
047A-2
500
46.7
63.0
20100.0
500
OFAF000H63
000
060A-2
500
60.0
63.0
20100.0
500
OFAF000H63
000
089A-2
1300
89.0
125.0
103000
500
OFAF00H125
00
115A-2
1300
115.0
125.0
103000
500
OFAF00H125
00
144A-2
1700
144.0
200
300000
500
OFAF0H200
0
171A-2
2300
171.0
250
600000
500
OFAF0H250
0
213A-2
3300
213.0
315
710000
500
OFAF1H315
1
276A-2
5500
276.0
400
1100000
500
OFAF2H400
2
3-phase
U
N
= 400 or 480 V
02A7-4
32
2.6
4
55
500
OFAF000H4
000
03A4-4
48
3.3
6
110
500
OFAF000H6
000
04A1-4
48
4.0
6
110
500
OFAF000H6
000
05A7-4
80
5.6
10
360
500
OFAF000H10
000
07A3-4
80
7.2
10
360
500
OFAF000H10
000
09A5-4
128
9.4
16
740
500
OFAF000H16
000
Summary of Contents for ACH580-01 Series
Page 1: ...ABB DRIVES FOR HVAC ACH580 01 drives 0 75 to 250 kW 1 to 350 hp Hardware manual...
Page 2: ...Related documents are listed on page 27...
Page 4: ......
Page 14: ...14 Table of contents...
Page 24: ...24 Safety instructions...
Page 34: ...34 Introduction to the manual...
Page 52: ...52 Operation principle and hardware description...
Page 112: ...112 Guidelines for planning the electrical installation...
Page 122: ...122 Electrical installation IEC IEC R6 R9 Screw A EMC DC B EMC AC C VAR 3 B 3 A 4 C...
Page 156: ...156 Electrical installation IEC IEC R4 0 5 0 6 N m 0 4 lbf ft 7 4 3 8 11 5 9 11 6 10 8 4...
Page 157: ...Electrical installation IEC 157 IEC R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 4 8...
Page 160: ...160 Electrical installation IEC IEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 210: ...210 Electrical installation North America UL NEC R4 4 lbf ft 7 4 3 11 5 9 11 6 10...
Page 211: ...Electrical installation North America 211 UL NEC 8 R5 4 6 11 11 10 3 5 7 9 0 4 lbf ft 4...
Page 214: ...214 Electrical installation North America UL NEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 222: ...222 Electrical installation North America UL NEC...
Page 242: ...242 Maintenance and hardware diagnostics...
Page 245: ...Technical data 245 See definitions and notes on page 247...
Page 308: ...308 Technical data...
Page 310: ...310 Dimension drawings Frame R1 IP21 UL Type 1 3AXD10000601652...
Page 311: ...Dimension drawings 311 Frame R1 IP55 UL Type 12 3AXD10000601699...
Page 312: ...312 Dimension drawings Frame R1 IP55 F278 UL Type 12 3AXD10000649451...
Page 313: ...Dimension drawings 313 Frame R2 IP21 UL Type 1 3AXD10000602398...
Page 314: ...314 Dimension drawings Frame R2 IP55 UL Type 12 3AXD10000602401...
Page 315: ...Dimension drawings 315 Frame R2 IP55 F278 UL Type 12 3AXD10000649654...
Page 316: ...316 Dimension drawings Frame R3 IP21 UL Type 1 3AXD10000602466...
Page 317: ...Dimension drawings 317 Frame R3 IP55 UL Type 12 3AXD10000602519...
Page 318: ...318 Dimension drawings Frame R3 IP55 E223 UL Type 12 3AXD10000649130...
Page 319: ...Dimension drawings 319 Frame R3 IP55 F278 F316 UL Type 12 3AXD10000649130...
Page 320: ...320 Dimension drawings Frame R4 IP21 UL Type 1 3AXD10000332430...
Page 321: ...Dimension drawings 321 Frame R4 IP55 UL Type 12 3AXD10000427933...
Page 322: ...322 Dimension drawings Frame R4 IP55 E223 UL Type 12 3AXD10000649283...
Page 323: ...Dimension drawings 323 Frame R4 IP55 F278 F316 UL Type 12 3AXD10000649283...
Page 324: ...324 Dimension drawings Frame R5 IP21 UL Type 1 3AXD10000412280...
Page 325: ...Dimension drawings 325 Frame R5 IP55 UL Type 12 3AXD10000415964...
Page 326: ...326 Dimension drawings Frame R5 IP55 E223 UL Type 12 3AXD10000687928...
Page 327: ...Dimension drawings 327 Frame R5 IP55 F278 F316 UL Type 12 3AXD10000687928...
Page 328: ...328 Dimension drawings Frame R6 IP21 UL Type 1 3AXD10000258705...
Page 329: ...Dimension drawings 329 Frame R6 IP55 UL Type 12 3AXD10000330667...
Page 330: ...330 Dimension drawings Frame R7 IP21 UL Type 1 3AXD10000258995...
Page 331: ...Dimension drawings 331 Frame R7 IP55 UL Type 12 3AXD10000330932...
Page 332: ...332 Dimension drawings Frame R8 IP21 UL Type 1 3AXD10000287670...
Page 333: ...Dimension drawings 333 Frame R8 IP55 UL Type 12 3AXD10000332446...
Page 334: ...334 Dimension drawings Frame R9 IP21 UL Type 1 3AXD10000287428...
Page 335: ...Dimension drawings 335 Frame R9 IP55 UL Type 12 3AXD10000334310...
Page 336: ...336 Dimension drawings...
Page 362: ...362 Safe torque off function...
Page 388: ...388 Optional I O extension modules...