Guidelines for planning the electrical installation 105
Implementing short-circuit and thermal overload protection
Protecting the drive and input power cable in short-circuits
Protect the drive and input cable with fuses as follows:
Size the fuses at the distribution board according to instructions given in chapter
, page
. The fuses will protect the input cable in short-circuit
situations, restrict drive damage and prevent damage to adjoining equipment in case
of a short-circuit inside the drive.
Circuit breakers, IEC
The protective characteristics of circuit breakers depend on the type, construction
and settings of the breakers. There are also limitations pertaining to the short-circuit
capacity of the supply network. Your local ABB representative can help you in
selecting the breaker type when the supply network characteristics are known.
WARNING!
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases can escape from
the breaker enclosure in case of a short-circuit. To ensure safe use, pay special
attention to the installation and placement of the breakers. Obey the manufacturer’s
instructions.
You can use the circuit breakers listed in chapter
, page
.
Other circuit breakers can be used with drive if they provide the same electrical
characteristics. ABB does not assume any liability whatsoever for the correct function
and protection with circuit breakers not listed below. Furthermore, if the
recommendations given by ABB are not obeyed, the drive can experience problems
that warranty does not cover.
Protecting the motor and motor cable in short-circuits
The drive protects the motor cable and a single motor in a short-circuit situation when
the motor cable is sized according to the nominal current of the drive. No additional
protection devices are needed.
~
~
M
3~
Summary of Contents for ACH580-01 Series
Page 1: ...ABB DRIVES FOR HVAC ACH580 01 drives 0 75 to 250 kW 1 to 350 hp Hardware manual...
Page 2: ...Related documents are listed on page 27...
Page 4: ......
Page 14: ...14 Table of contents...
Page 24: ...24 Safety instructions...
Page 34: ...34 Introduction to the manual...
Page 52: ...52 Operation principle and hardware description...
Page 112: ...112 Guidelines for planning the electrical installation...
Page 122: ...122 Electrical installation IEC IEC R6 R9 Screw A EMC DC B EMC AC C VAR 3 B 3 A 4 C...
Page 156: ...156 Electrical installation IEC IEC R4 0 5 0 6 N m 0 4 lbf ft 7 4 3 8 11 5 9 11 6 10 8 4...
Page 157: ...Electrical installation IEC 157 IEC R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 4 8...
Page 160: ...160 Electrical installation IEC IEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 210: ...210 Electrical installation North America UL NEC R4 4 lbf ft 7 4 3 11 5 9 11 6 10...
Page 211: ...Electrical installation North America 211 UL NEC 8 R5 4 6 11 11 10 3 5 7 9 0 4 lbf ft 4...
Page 214: ...214 Electrical installation North America UL NEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 222: ...222 Electrical installation North America UL NEC...
Page 242: ...242 Maintenance and hardware diagnostics...
Page 245: ...Technical data 245 See definitions and notes on page 247...
Page 308: ...308 Technical data...
Page 310: ...310 Dimension drawings Frame R1 IP21 UL Type 1 3AXD10000601652...
Page 311: ...Dimension drawings 311 Frame R1 IP55 UL Type 12 3AXD10000601699...
Page 312: ...312 Dimension drawings Frame R1 IP55 F278 UL Type 12 3AXD10000649451...
Page 313: ...Dimension drawings 313 Frame R2 IP21 UL Type 1 3AXD10000602398...
Page 314: ...314 Dimension drawings Frame R2 IP55 UL Type 12 3AXD10000602401...
Page 315: ...Dimension drawings 315 Frame R2 IP55 F278 UL Type 12 3AXD10000649654...
Page 316: ...316 Dimension drawings Frame R3 IP21 UL Type 1 3AXD10000602466...
Page 317: ...Dimension drawings 317 Frame R3 IP55 UL Type 12 3AXD10000602519...
Page 318: ...318 Dimension drawings Frame R3 IP55 E223 UL Type 12 3AXD10000649130...
Page 319: ...Dimension drawings 319 Frame R3 IP55 F278 F316 UL Type 12 3AXD10000649130...
Page 320: ...320 Dimension drawings Frame R4 IP21 UL Type 1 3AXD10000332430...
Page 321: ...Dimension drawings 321 Frame R4 IP55 UL Type 12 3AXD10000427933...
Page 322: ...322 Dimension drawings Frame R4 IP55 E223 UL Type 12 3AXD10000649283...
Page 323: ...Dimension drawings 323 Frame R4 IP55 F278 F316 UL Type 12 3AXD10000649283...
Page 324: ...324 Dimension drawings Frame R5 IP21 UL Type 1 3AXD10000412280...
Page 325: ...Dimension drawings 325 Frame R5 IP55 UL Type 12 3AXD10000415964...
Page 326: ...326 Dimension drawings Frame R5 IP55 E223 UL Type 12 3AXD10000687928...
Page 327: ...Dimension drawings 327 Frame R5 IP55 F278 F316 UL Type 12 3AXD10000687928...
Page 328: ...328 Dimension drawings Frame R6 IP21 UL Type 1 3AXD10000258705...
Page 329: ...Dimension drawings 329 Frame R6 IP55 UL Type 12 3AXD10000330667...
Page 330: ...330 Dimension drawings Frame R7 IP21 UL Type 1 3AXD10000258995...
Page 331: ...Dimension drawings 331 Frame R7 IP55 UL Type 12 3AXD10000330932...
Page 332: ...332 Dimension drawings Frame R8 IP21 UL Type 1 3AXD10000287670...
Page 333: ...Dimension drawings 333 Frame R8 IP55 UL Type 12 3AXD10000332446...
Page 334: ...334 Dimension drawings Frame R9 IP21 UL Type 1 3AXD10000287428...
Page 335: ...Dimension drawings 335 Frame R9 IP55 UL Type 12 3AXD10000334310...
Page 336: ...336 Dimension drawings...
Page 362: ...362 Safe torque off function...
Page 388: ...388 Optional I O extension modules...