72 OI/266/HART-EN Rev. D
| 2600T Series Pressure transmitters
266 Models - HART
System safety requirement assignment I/O system response time
The total system response time is determined by the following elements:
- Sensor detection time,
- Logic solver time;
- Actuator response time;
The total system response time must be less than the process safety time. To ensure a safe operation of the system, the scan
rate of each section of the logic solver multiplied by the number of channels shall be taken into account together with the safety
time of actuator and sensor response time.
System structure
System configuration drawings shall be available to describe the equipment and interfaces required for a complete operational
system. The system must be fully operational before start-up.
Safety requirement allocation
Each safety function, with its associated safety integrity requirement, shall be allocated to the designated safety related systems
taking into account the risk reductions achieved by the other technology safety-related systems and external risk reduction
facilities, so the necessary risk reduction for that safety function is achieved.
The allocation indicated shall be done in such a way that all safety functions are allocated and the safety integrity requirements
are met for each safety function.
Safety routines
Safety additional requirements may be defined in order to ensure the correct functionality of sequences in the Safety
Instrumented System.
Commissioning
Overall system functionality
The activity to validate the required safety functionality of the system together with the pressure transmitter according to the
Safety Requirement Specification is the Pre-Startup Acceptance test.
Faults outside the functional safety
The redundant algorithms and the electronics are designed to detect all the internal hardware faults therefore the transmitter
diagnostic is not able to detect faults related to the process and to the installation configuration. In the following table the known
weaknesses resulting from the transducer FMEA (Failure Mode and Effect Analysis) are listed.
– Assembled material at the pipes of the transmitter, blockage of pipe.
– Application outside specified temperature range.
– Excess of temperature
– Assembled gas at the transmitter, if the transmitter is mounted above the process line
– Overload pressure, high peak pressure pulses in process lines
– Penetration of hydrogen, diaphragm crack in applications with hydrogen process medium.
– Thin walled diaphragm, leaky diaphragm in applications with abrasive medium.
– Thin walled diaphragm, leaky diaphragm in applications with corrosive medium.
– Higher diaphragm stiffness, crack in application with contamination of metal ions
– Mechanical damage through cleaning, damage of the coating, corrosion.
Other considerations
The alarm levels of the transmitter (down-scale or up-scale) can be selected by the user. As default all the 266 devices are
configured with up-scale alarm. For some faults (e.g. crystal breakdown), the output will latch at 3.6 mA even if the up scale alarm
level is selected.
Summary of Contents for 266 HART Series
Page 40: ...40 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Device Set up ...
Page 41: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 41 ...
Page 42: ...42 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 43 ...
Page 44: ...44 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Display ...
Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 45 ...
Page 46: ...46 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 48: ...48 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Calibrate ...
Page 49: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 49 Totalizer ...
Page 50: ...50 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 51 ...
Page 52: ...52 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Diagnostics ...
Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 53 Device Info ...
Page 54: ...54 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Communication ...
Page 77: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 77 ...
Page 78: ...78 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 79: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 79 ...