2600T Series Pressure transmitters |
OI/266/HART-EN Rev. D 61
– Configuration related error messages.
Error message Tx LCD message Possible cause
Suggested action
Tx response
C088.030
Input Simulation
Active
The P-dP Value produced in output is
derived by the value simulated in input
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove the
input simulation)
no effect
C088.030
Input Simulation
Active
The Static Pressure Value produced in out-
put is derived by the value simulated in input
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove the
input simulation)
no effect
C088.030
Input Simulation
Active
The Sensor Temperature Value produced in
output is derived by the value simulated in
input
Use a HART configurator (DTM - Hand held) to place
device back in to normal operating mode (Remove the
input simulation)
no effect
M014.037
Configuration Error Refer to the Instruction manual to under-
stand the possible cause of this error
Use a HART configurator (DTM - Hand held) to correct
the configuration
no effect
M020.042
Replace Info
The Electronics or the Sensor have been
changed but the replacement operation has
not been executed
The replacement operation must be executed: Move the
SW 1 of the electronics in position 1 = Enable replace
mode -Select the SW 2 the element that has been
changed between new Sensor or new electronics
-Power Cycle the device -Move the SW 1 of the elec-
tronics in position 0
no effect
M020.042
Replace Info
The Electronics or the Sensor have been
changed and a replacement operation for a
new sensor has to be executed.
The replacement operation must be executed: Only the
data of the electronics can be copied into the sensor-
Move the SW 1 to Enable replace mode (1)-Select with
the SW 2 to New Sensor (1)-Power Cycle the device-
Move the SW 1 to Disable replace mode (0)
no effect
M020.042
Replace Info
The Electronics or the Sensor have been
changed,
The replacement has been enabled but with
a wrong direction (SW 2 = 0).
Change the replacement direction (if possible)-The SW 1
is already set to Enable replace mode (1)-Select with the
SW 2 to New Sensor (1)-Power Cycle the device-Move
the SW 1 to Disable replace mode (0)
no effect
– Operation related error messages
Error message Tx LCD message
Possible cause
Suggested action
Tx response
M024.036
Power Supply Warning
the Device Power Supply is close to the lowest
acceptable limit
Check the Voltage at the terminal block and if
it is not within the valid range check the exter-
nal power supply
no effect
M024.036
Power Supply Warning
the Device Power Supply is close to the highest
acceptable limit
Check the Voltage at the terminal block and if
it is not within the valid range check the exter-
nal power supply
no effect
M022.041
Electronic Temperature
Out of Limits
The Electronics temperature is out of its lower
acceptable limit . The circuitry for the sampling of
the Electronics Temperature has failed.
The Electronics should be replaced as soon
as possible.
no effect
M022.041
Electronic Temperature
Out of Limits
The Electronics temperature is out for its Higher
acceptable limit. The circuitry for the sampling of
the Electronics Temperature has failed.
The Electronics should be replaced as soon
as possible.
no effect
Summary of Contents for 266 HART Series
Page 40: ...40 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Device Set up ...
Page 41: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 41 ...
Page 42: ...42 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 43 ...
Page 44: ...44 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Display ...
Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 45 ...
Page 46: ...46 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 48: ...48 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Calibrate ...
Page 49: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 49 Totalizer ...
Page 50: ...50 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 51 ...
Page 52: ...52 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Diagnostics ...
Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 53 Device Info ...
Page 54: ...54 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Communication ...
Page 77: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 77 ...
Page 78: ...78 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 79: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 79 ...