62 OI/266/HART-EN Rev. D
| 2600T Series Pressure transmitters
266 Models - HART
– Process related error messages.
Error message Tx LCD message Possible cause
Suggested action
Tx response
F104.032
Pressure Overrange
This effect could be produced by other equipment on the pro-
cess, (valves…..). Exceeding the pressure range can cause
reduced accuracy or mechanical damage to the diaphragm
material and may require calibration/replacement.
The compatibility of pressure trans-
mitter model and process conditions
has to be checked. A different trans-
mitter type could be required
no effect
F102.004
P-dP Out Of Limits The measurement range has not been correctly calculated OR
an incorrect transducer model has been selected.
The compatibility of pressure trans-
mitter model and process conditions
has to be checked. Probably a differ-
ent transmitter type is required.
no effect
F100.005
Static Pressure Out
of Limits
The static pressure of the process exceeds the limit of the sen-
sor. Exceeding the Static Pressure can reduce accuracy,
mechanically damage the diaphragm and may require calibra-
tion/replacement. An incorrect transducer model could have
been selected.
The compatibility of pressure trans-
mitter model and process conditions
has to be checked.
Probably a different transmitter type
is required.
no effect
S054.006
Sensor Temperature
Out of Limits
The temperature of the process environment affects the pres-
sure transmitter; Excess temperature can reduce accuracy,
degrade device components and may require calibration/
replacement.
The compatibility of pressure trans-
mitter model and process conditions
has to be checked.
A different installation type could be
required e.g. use of remote seals.
no effect
S052.031
Max Working Pres-
sure Exceeded
The static pressure of the process exceeds the max working
Pressure supported by the transmitter. Exceeding the Max
Working Pressure can mechanically damage the process con-
nections (flanges, pipes….) and/or be dangerous
The compatibility of pressure trans-
mitter model and process conditions
has to be checked.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its Low
scaling limit and no longer represents the true applied process.
The Analog Output (4-20 mA) is saturated to the configured
Saturation Limit Low.
Adjust the Saturation Limit or the
working range if possible.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its High
scaling limit and no longer represents the true applied process.
The Analog Output (4-20 mA) is saturated to the configured
Saturation Limit High.
Adjust the Saturation Limit or the
working range if possible.
no effect
M018.038
PILD Output
One (HIGH or LOW) or both connections between the pressure
sensor and the process is blocked either by plugging or closed
valves.
Check valves and impulse line.
Clean impulse line if necessary and
initiate PILD training
no effect
M016.039
PILD-Changed
Operating
Conditions
Process conditions have changed to an extent that new set-
tings for the PILD algorithm are needed.
A new Training is necessary for this
new process condition.
no effect
Summary of Contents for 266 HART Series
Page 40: ...40 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Device Set up ...
Page 41: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 41 ...
Page 42: ...42 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 43 ...
Page 44: ...44 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Display ...
Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 45 ...
Page 46: ...46 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 48: ...48 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Calibrate ...
Page 49: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 49 Totalizer ...
Page 50: ...50 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 51 ...
Page 52: ...52 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Diagnostics ...
Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 53 Device Info ...
Page 54: ...54 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART Communication ...
Page 77: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 77 ...
Page 78: ...78 OI 266 HART EN Rev D 2600T Series Pressure transmitters 266 Models HART ...
Page 79: ...2600T Series Pressure transmitters OI 266 HART EN Rev D 79 ...