. . .8 Error messages
. . .Error states and alarms
Error code
Description
Possible cause
Suggested /recommended action
Current output
S098.034
The result of the selected
Calculation type (Primary-
Secondary unit or Viceversa) is
outside its Low Saturation Limit
The analog output for the Primary
Variable (PV) is beyond its Low
scaling limit and no longer
represents the true applied process.
The Analog Output (4-20 mA) is
saturated to the configured
Saturation Limit Low.
Adjust the Saturation Limit or the working range
if possible.
no effect
The result of the selected
Calculation type (Primary-
Secondary unit or Viceversa) is
outside its High Saturation Limit
The analog output for the Primary
Variable (PV) is beyond its High
scaling limit and no longer
represents the true applied process.
The Analog Output (4-20 mA) is
saturated to the configured
Saturation Limit High
Adjust the Saturation Limit or the working range
if possible.
F106.035
The Analog Output Current could
deviate from the correct value due
to D to A problems
The D to A converter is not properly
Calibrated/Trimmed
Perform an Output Trimming and if the error
persist the electronics (communication board)
must be replaced
UP/DW ALARM
Wrong device configuration could
produce a digital value that the D to
A converter cannot manage
The device is not properly
configured
Check the Device configuration.
M024.036
The device continues to work
without problems but the power
supply level is close to a threshold
that could preclude the correct
functionality
The Device Power Supply is close to
the lowest acceptable limit
Check the Voltage at the terminal block and if it is
not within the valid range check the external
power supply
no effect
The device continues to work
without problems but the power
supply level is close to a threeshold
that could preclude the correct
functionality
The Device Power Supply is close to
the highest acceptable limit
Check the Voltage at the terminal block and if it is
not within the valid range check the external
power supply
S051.037
The Process Pressure measured by
the Secondary unit sensor is higher
than the acceptable mechanical
limit of the process connection
elements.
The measured process pressure
exceeds the limit of the max
working Pressure supported by the
Secondary unit. Exceeding the Max
Working Pressure can mechanically
damage the process connections
(flanges, pipes, etc) and/or be
dangerous
The compatibility of the process connection type
and material with process conditions has to be
checked. A different installation type could be
required e.g. use of remote seals.
no effect
F103.038
An overpressure has been detected
by the Secondary unit sensor
This effect could be produced by
other equipment on the process,
(valves, etc). Exceeding the pressure
range can cause reduced accuracy
or mechanical damage to the
diaphragm material and may
require calibration/replacement.
The compatibility of pressure transmitter model
and process conditions has to be checked. A
different transmitter type could be required
no effect
F115.039
The Primary unit at the start up has
detected that the connected
Secondary unit has characteristics
not compatible with it and for this
reason the DDS system doesn't
work
The Primary and Secondary units
have Different Module type or
sensor limits (Upper Range Limit)
Change the Secondary unit with another one
having the same sensor type (gauge or Absolute)
and with the same sensor limits of the Primary
unit
UP/DW ALARM
F108.040
The reading of the 4-20mA output
signal is too different from what
should have been generated
The output circuit could be broken
or not correctly calibrated
Perform an Output Trimming and if the error
persist the electronics (communication board)
must be replaced
UP/DW ALARM
S022.041
The Accuracy of the D/A conversion
could be decreased.
The Output 4/20 mA signal
representing the measure could be
not correctly compensated.
The electronics (communication
board) temperature is out of its
lower acceptable limit.
The electronics (communication board) should be
replaced as soon as possible.
no effect
M022.041
The Accuracy of the D/A conversion
could be decreased.
The Output 4/20 mA signal
representing the measure could be
not correctly compensated.
The electronics (communication
board) temperature is out of its
higer acceptable limit.
The electronics (communication board) should be
replaced as soon as possible.
no effect
Summary of Contents for 266 DDS
Page 30: ...Device Set up 30 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 31: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 31 ...
Page 32: ...32 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 33: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 33 ...
Page 34: ...Display 34 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 35: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 35 ...
Page 36: ...36 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 41: ...Device Info 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 41 ...
Page 42: ...Communication 42 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 59: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 59 Notes ...