Error code
Description
Possible cause
Suggested /recommended action
Current output
M020.042
The Replace operation is required
after the changing of the
electronics or of the sensor
The electronics (communication
board) or the Sensor have been
changed but the replacement
operation has not been executed
"The replacement operation must be executed:
-Move the SW 1 of the electronics (communication
board) in position 1 = Enable replace mode
-Select the SW 2 the element that has been
changed between new Sensor or new electronics
(communication board)
-Power Cycle the device
-Move the SW 1 of the electronics (communication
board) in position 0"
no effect
The Replace operation is required
after the changing of the
electronics or of the sensor
The electronics (communication
board) or the Sensor have been
changed and a replacement
operation for a new sensor has to
be executed.
"The replacement operation must be executed:
Only the data of the electronics (communication
board) can be copied into the sensor
-Move the SW 1 to Enable replace mode (1)
-Select with the SW 2 to New Sensor (1)
-Power Cycle the device
-Move the SW 1 to Disable replace mode (0)
"
no effect
The Replace operation has been
attempted but with wrong direction
The electronics (communication
board) or the Sensor have been
changed, The replacement has been
enabled but with a wrong direction
(SW 2 = 0)
"Change the replacememt direction (if possible)
-The SW 1 is already set to Enable replace mode
(1)
-Select with the SW 2 to New Sensor (1)
-Power Cycle the device
-Move the SW 1 to Disable replace mode (0)
"
no effect
F105.043
The Accuracy of the D/A conversion
could be decreased.
The Output 4/20 mA signal
representing the measure is
compensated to the last valid
temperature
The circuitry for the sampling of the
electronics (communication board)
temperature has failed.
The electronics (communication board) should be
replaced as soon as possible.
UP/DW ALARM
F117.044
The data in the Secondary unit
sensor memory are corrupted
precluding the correct functionality
of the device
Secondary unit Sensor memory
corrupted
The Secondary unit Sensor must be replaced
UP/DW ALARM
M027.045
The device continues to work
without problems but the new
settings for the Secondary unit
sensor can be lost after a power
cycle because the backuped
configuration is not updated
Writings to the Secondary unit
Sensor non-Volatile Memory was
not successful
The Secondary unit Sensor should be replaced as
soon as possible.
no effect
F119.046
The Basic signal of the Secondary
unit sensor is no longer available.
The transducer is not in a condition
to generate a valid signal.
The sensor signal of the Secondary
unit is not being updated correctly
as a result of electronics
(communication board) failure,
sensor error or a poorly connected
sensor cable.
Check cable connection, check sensor and if
problem persists, the Secondary unit sensor must
be replaced.
UP ALARM
Summary of Contents for 266 DDS
Page 30: ...Device Set up 30 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 31: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 31 ...
Page 32: ...32 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 33: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 33 ...
Page 34: ...Display 34 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 35: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 35 ...
Page 36: ...36 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 41: ...Device Info 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 41 ...
Page 42: ...Communication 42 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 59: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 59 Notes ...