For or additional information, refer to the operating
instructions included with the handheld terminal.
If the transmitter has been configured in the factory according
to customer specifications for the measuring point, all you
have to do is mount the transmitter as prescribed (to correct
potential zero shifts, refer to the section “Correcting the zero
shift”), and switch it on. The measuring point will now be
ready for use.
If, however, you wish to make changes to the configuration, a
handheld terminal or - preferably - a graphical user interface
(FDI/DTM) is required. This DTM tool renders the device fully
configurable. It supports the HART and can be run on a PC or
laptop, or as part of an automation system.
Refer to the installation manual provided with the software for
the steps required to install the operating tool. The most
important parameters can be set via the path “Parametrize_
Differential Pressure Measurement”.
The program offers the option of configuring, polling, and
testing the transmitter.
In addition, offline configuration can be performed by means
of an internal database.
Each configuration step is subject to a plausibility check.
You can call up context-sensitive help at any time by pressing
the “F1” key. Immediately after you have received the
transmitter or before you change the configuration, we
recommend that you save the existing configuration data to
a separate data storage medium, via the path “File_Save”.
Configuration with the graphical user interface (DD/FDI) -
System requirements
• Operating control program (e.g., ABB Field Information
Manager)
• DD/FDI (Device Type Manager; graphical user interface)
• Operating system (depending on the respective control
program)
To operate the ABB Field Information Manager, please refer to
the relevant operating instruction.
Advanced HART software revision history
Revision
Description
Release
date
From To
147.1.1
First release
05/2022
2 6 6 DDS H A RT |
P R E SSU R E T R A N SM I T T ER S | O I/ 2 6 6 D DS - EN R E V. B
45
Summary of Contents for 266 DDS
Page 30: ...Device Set up 30 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 31: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 31 ...
Page 32: ...32 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 33: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 33 ...
Page 34: ...Display 34 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 35: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 35 ...
Page 36: ...36 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 41: ...Device Info 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 41 ...
Page 42: ...Communication 42 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 59: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 59 Notes ...