Error code
Description
Possible cause
Suggested /recommended action
Current output
F120.016
The Basic signal of the Primary unit
sensor is no longer available.
The transducer is not in a condition
to generate a valid signal.
The sensor signal of the Primary
unit is not being updated correctly
as a result of electronics
(communication board) failure,
sensor error or a poorly connected
sensor cable.
Check cable connection, check sensor and if
problem persists, the Primary unit sensor must
be replaced.
UP ALARM
Primary Unit Sensor and/or the
connected electronics are
incompatible
The Primary unit sensor model/
version is no longer compatible with
the connected electronic version
The Primary unit sensor must be replaced
F118.017
The data in the Primary unit sensor
memory are corrupted precluding
the correct functionality of the
device
Primary unit Sensor memory
corrupted
The Primary unit Sensor must be replaced
UP/DW ALARM
M028.018
The device continues to work
without problems but any
replacement operation relating the
Primary unit is compromised
because the backuped
configuration is not updated
Writings to the Primary unit Sensor
non-Volatile Memory was not
successful
The Primary unit Sensor should be replaced as
soon as possible.
no effect
M030.020
The Primary unit sensor has
problem to communicate with the
Communication Board due to
problem in the transmitter circuit of
the electronics or in receiver circuit
of the sensor
Exchange of data between the
Electronics (Communication Board)
and Primary unit Sensor have
problems
Power cycle the device and retry the operation, if
the error persist the electronics/Comm.Board
should be replaced as soon as possible.
no effect
F116.023
The device data loaded at the start
up are corrupted precluding the
correct functionality of the device
Electronic memory corrupted
The electronics (communication board) must be
replaced
UP/DW ALARM
M026.024
The device continues to work
without problems but after the next
power cycle the new configuration
will be lost
Writings to the electronic non-
Volatile Memory was not successful
The electronics (communication board) should be
replaced as soon as possible.
no effect
C088.030
The Primary unit Process Value is
simulated and do not represent the
real Process value.
The Pressure Value produced by the
Primary unit Sensor is derived by
the value simulated in input
Use an HART configurator to place device back
into normal operating mode (Remove the input
simulation)
no effect
The Secondary unit Process Value is
simulated and do not represent the
real process value
The Pressure Value produced by the
Secondary unit Sensor is derived by
the value simulated in input
Use a HART configurator to place device back into
normal operating mode (Remove the input
simulation)
The Temperature Value of the
Primary unit sensor is simulated
and do not represents the real
Primary Sensor Temperature
The Sensor Temperature of the
Primary unit is derived by the value
simulated in input
Use a HART configurator to place device back into
normal operating mode (Remove the input
simulation)
The Temperature Value of the
Secondary unit sensor is simulated
and do not represents the real
Secondary unit sensor Temperature
The Sensor Temperature of the
Secondary unit is derived by the
value simulated in input
Use a HART configurator to place device back into
normal operating mode (Remove the input
simulation)
S052.031
The Process Pressure measureed by
the Primary sensor is higher than
the acceptable mechanical limit of
the process connection elements.
The measured process pressure
exceeds the limit of the max
working Pressure supported by the
primary unit. Exceeding the Max
Working Pressure can mechanically
damage the process connections
(flanges, pipes, etc) and/or be
dangerous
The compatibility of the process connection type
and material with process conditions has to be
checked. A different installation type could be
required e.g. use of remote seals.
no effect
F104.032
An overpressure has been detected
by the Primary unit sensor
This effect could be produced by
other equipment on the process,
(valves, etc). Exceeding the pressure
range can cause reduced accuracy
or mechanical damage to the
diaphragm material and may
require calibration/replacement.
The compatibility of pressure transmitter model
and process conditions has to be checked. A
different transmitter type could be required
no effect
C090.033
Analog output current fixed. The
primary variable (PV) analog and
digital analog outputs will not
respond to the applied process.
The analog and digital analog
outputs for the Primary Variable
(PV) are held at the requested value.
Device is in fixed current (Loop
Test) mode.
Use a HART configurator to place device back into
normal operating mode (Remove from Loop Test -
Fixed output mode)
no effect
Summary of Contents for 266 DDS
Page 30: ...Device Set up 30 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 31: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 31 ...
Page 32: ...32 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 33: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 33 ...
Page 34: ...Display 34 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 35: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 35 ...
Page 36: ...36 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 41: ...Device Info 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 41 ...
Page 42: ...Communication 42 266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B ...
Page 59: ...266 DDS HART PRESSURE TR ANSMITTERS OI 266DDS EN REV B 59 Notes ...