4.5.3 Installation of the bushing with the fixed bottom contact
Overview
This procedure is only applicable for bushings with a fixed bottom contact.
The fixed bottom contact is installed when it is delivered from Hitachi ABB Power Grids.
CAUTION!
Do not remove the fixed bottom contact.
G007609
36 Fixed bottom contact
Procedure
1.
Lower the bushing into the transformer.
CAUTION!
Do not damage the stud bolts on the
transformer. There is a risk of metal
falling into the transformer.
NOTE!
Plastic sleeves put on two or three of
the stud bolts will help to guide the
flange, and will prevent damage to the
stud bolts.
G007618