Manual Corrigo E Ventilation, revision Q
Configuration
95
Alarm text
Pri Description
11 External switch
C
"External switch" activated
12 External alarm
B
External alarm activated
13 Supply Air control error B
Supply air temp deviates too much from the setpoint
for too long.
14 Humidity control error
-
The room humidity deviates too much from the
setpoint.
15 High supply air temp
B
Supply air temp too high
16 Low supply air temp
B
Supply air temp too low
17 Supply air temp max
-
Maximum limiting of supply air temp active
18 Supply air temp min
-
Minimum limiting of supply air temp active
19 High room temp
B
Room temp too high during room temp control
20 Low room temp
B
Room temp too low during room temp control
21 High extract air temp
B
High extract air temp during extract air control
22 Low extract air temp
B
Low extract air temp during extract air control
23 Electric heating is
overheated
A
Heater high temperature limit switch activated
24 Frost risk
B
Frost protection function is overriding the control of
the heater output
25 Low frostguard temp
A
Frost protection temperature below frost limit value
26 Low efficiency
B
Heat exchanger efficiency below limit value
27 Sensor error Outdoor
temp
B
Malfunction of connected sensor
28 Analogue de-icing
-
Exchanger de-icing activated by de-icing sensor
29 Rotation guard
exchanger
B
Exchanger rotation sentinel alarm activated
30 Fire damper is out of
operation
B
Fire damper exercise test failed
31 Supply Air Fan control
error
-
Supply air pressure deviates too much from the
setpoint for too long.
32 Extract Air Fan control
error
-
Extract air pressure deviates too much from the
setpoint for too long.
33 Supply Air Fan external
operation
C
SAF run-signal received when unit is stopped
34 Extract Air Fan external
operation
C
EAF run-signal received when unit is stopped
35 Ventilation Manual
mode
C
The unit is in manual mode
36 Manual supply air
control
C
Supply air temp controller in manual control
37 Manual supply Air Fan
mode
C
Supply air fan in manual control
38 Manual Supply Air
C
The SAF is in manual mode
39 Manual Extract Air Fan
mode
C
Extract air fan in manual control
40 Manual Extract Air
C
The EAF is in manual mode
41 Manual Heater Control C
The heater is in manual mode
42 Manual exchanger
control
C
Heat exchanger output in manual control
43 Manual cooler control
C
Cooling output in manual control