86
Configuration
Manual Corrigo E Ventilation, revision Q
Blocking the DX cooling at low outdoor temp
Outdoor temperature dependent blocking of DX cooling is individually settable for each cooling
step. If the outdoor temperature is below the set value, it is not possible to activate the cooling step.
The function has a 1K hysteresis, i.e. if a cooling step is blocked, it can only be activated again
when the outdoor temperature has risen to 1K above the set value.
Block DX-cooling,
step1, at outdoor temp.
lower than 13.0 °C
Blocking of DX cooling on cooling pump alarm
DX cooling can be blocked on activation of the cooling pump alarm.
Block DX-cooling on
alarm
”Run error P1-
cooler”:No
Override of reduced speed for DX cooling
Override to normal quantity of air for DX cooling when the unit runs on reduced quantity of air. The
fans can be set to normal operation when cooling is required at high outdoor temperatures (e.g.
>14°C, the same temperature limit as for blocking of DX cooling).
Force normal
speed if active
DX-cooling:Yes
16.10 Pump control
P1-Heating
P1-Exchanger
P1-Cooling
In these menus the parameters for pump control are set.
If, for any of the control circuits, no output is configured for pump control these settings will be
ignored.
P1 Heating
Pump stop: Yes
Stop delay: 5 min
Outd. Temp stop: 10°C
Differential: 1.0°C
P1 Exchanger
P1-Exchanger
Stop delay: 5 min
P1 Cooling
P1-Cooling
Stop delay: 5 min