94
Configuration
Manual Corrigo E Ventilation, revision Q
If a sensor is configured in the intake duct (”intaketemp”) this temperature will be compared with
the outdoor temperature. If the temperature in the intake duct does not exceed the outdoor
temperature by more than 1°C (adjustable) 5 minutes (fixed) after start-up when using preheating,
preheating will be aborted. The same conditions apply to precooling, i.e. if the intake temperature is
not more than 1°C (adjustable) cooler than the outdoor temperature, precooling will be aborted.
Pretreatment always starts at start-up of the unit, if the outdoor temperature so permits. If
pretreatment is aborted due to a small difference between the intake temperature and the outdoor
temperature, pretreatment will be blocked for 6 hours. Then pretreatment will start (if the outdoor
temperature so permits) and run for at least 5 minutes.
Outdoortemp for
activating
preheating: 8.0 °C
precooling: 19.0°C
Minimum diff.
outdoortemp-
intaketemp: 1.0°C
16.27 Alarm setting
Permits configuration of all alarms.
Select the appropriate alarm number (from the alarm list). The alarm text for the alarm will be
displayed and the alarm priority can be set; "A-alarm", "B-alarm", "C-alarm" or "not active". The
extra stop function gives, for each alarm, the option to stop or not stop the unit on alarm activation.
Run Error supply air
Priority: B-alarm
Extra stop function
Active
Alarm text
The alarm text that should be shown in the display when there is an alarm can be changed using E
tool
©
. For more information, see the E tool
©
manual.
Alarm list
The alarm text and priority columns show the factory set values.
Alarm text
Pri Description
1 Run Error Supply Air
Fan
B
Malfunction Supply air fan
2 Run Error Extract Air
Fan
B
Malfunction Extract air fan
3 Run Error P1-Heater
B
Malfunction pump, Heating circuit
4 Run Error P1-Cooler
B
Malfunction pump, Cooling circuit
5 Run Error P1-
Exchanger
B
Malfunction pump, Liquid connected exchanger
6 Filter guard
B
Filter guard pressure switch activated
7 Flow switch
B
Flow switch activated
8 External frost guard
A
External Frost protection thermostat activated
9 Deicing pressure guard -
Exchanger de-icing pressure switch activated
10 Fire alarm
A
Fire alarm activated