
62
Temperature
Manual Corrigo E Ventilation, revision Q
Outdoor comp. setp.
10.0°C = 18.0°C
15.0°C = 18.0°C
In-between-values are calculated using straight lines between breakpoints. Setpoints for
temperatures lower than the lowest breakpoint and higher than the highest breakpoint are calculated
by extending the line between the two last breakpoints at either end.
Example: At the lower end the setpoint is increasing by 1°C for every 5 °C lowering of the outdoor
temperature. So the setpoint at –23°C would be 25°C + .6x 1.0°C = 25.6°C.
Setpoint. Control mode 3 and 5: Cascaded room temperature control.
Room temp.1
Actual: 22.0°C
Setpoint: 21.5°C
In control mode five, the setpoint is used when cascade connected room control is active.
Submenu for setting the min and max limitation temperatures for the supply air.
If cascade control
max/min supply setp.
Max: 30.0°C
Min: 12.0°C
If two room sensors have been configured you will also get the following menu:
Room temp.2
Actual: 21.8°C
Setpoint.
Control mode 4: Cascade connected extract air control.
Control mode 6: Outdoor temperature-dependent supply or extract air control.
Extract air temp.
Actual: 21.0°C
Setpoint: 21.1°C
In control mode six, the setpoint is used when cascade connected extract air control is active.
Submenu for setting the min. and max. limitation temperatures for the supply air.
If cascade control
max/min supply setp.
Max: 30.0°C
Min: 12.0°C