EBM
EBM frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read from the frequency converter:
Address
Modbus register
Name
Scaling
Type
27
30027,40027
FB Status word
-
Binary
511
3051140511
Cumulative output
0.1
kWh
527
30527,40527
Motor frequency
0.1
+/- Hz
508
30508,40508
Motor current
0.1
A
510
30510,40510
Motor output
0.01
kW
505
30505,40505
DC voltage
1
V
30
30030,40030
Active error
-
Error code
The following signals can be used to control fan speed:
Address
Modbus register
Name
Scaling
Type
1
30001,30001
Control Word
-
Binary
44
30044,40044
FB Setpoint speed
0.1
Hz
48
30048,40048
Password
-
Binary
49
30049,40049
Password
-
Binary