Manual Corrigo E Ventilation, revision Q
Configuration
87
For a detailed description of pump functions, see the section Pump control.
16.11 Free cooling
Free cool active:Yes
Outd. temp activation
22.0°C
Outd. Temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
Free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 min
Fan output
when free cooling
SAF: 0 %
EAF: 0 %
Outdoor sensor
placed in intake
channel
No
For detailed description, see section 5.1.6 Free cooling.
16.12 Support control
Note: If you select the function support control without EAF (extract air fan), a recirculation damper
must be used. See more in section 5.1.5.
Support control
Active: Yes
EAF running during
support contr: Yes
Minimum running time
Min. run time for
support ctrl: 20 min
For detailed description, see 5.1.5 Support control.