background image

Integrated Access Controller  – Installation manual  

All rights reserved. © AAT HOLDING S.A.

 

 

1.   Introduction 

 

 
 
 
 
 

 
 
 
 

 
 
 
 
 

 
 

 KZ-1000-IP-U 

 KZ-1000-IP-M  

 

 

The KZ-1000-IP controller has been designed for access control system and 

to be mounted on a wall without any additional enclosure. 32 bit processor en-
sures fast and reliable data processing.  This is one door controller. With addi-

tional reader (also with keypad) it can use for two way control. Recommended 
supply power type AWZ-200 plus 7Ah battery. 

 

It’s possibility to set one from four identification mode: 

 

- Card only (default mode) 

 

- PIN only  

 

- Card or PIN  

 

- Card + PIN 

 

KZ-1000-IP can work in standalone (programming from keypad) or in net-

work mode. In network mode it can work on-line or off-line with supervisor KaDe 
Premium Plus software on PC.  

KZ-1000-IP include following components in one plastic cabinet: 

 

controller module for 1 door 

 

card reader - 125 kHz ISO UNIQUE - model KZ-1000-U-IP 

       or 

 

card reader - 13,56 MHz MIFARE – model KZ-1000-M-IP 

 

 

keypad for PIN with bell button

 

 

LED and Buzzer

 

 

anti-disassemble sensor  

Summary of Contents for KZ-1000-IP-U

Page 1: ...Installation Manual INTEGRATED ACCESS CONTROLLER KZ 1000 IP U KZ 1000 IP M VERSION 1 0...

Page 2: ...served AAT HOLDING S A 2 1 Introduction 3 2 Controller technical data 5 3 Controller wiring diagram 6 4 Controller installation 8 5 Management in standalone mode 9 6 Programming codes table 14 7 Manag...

Page 3: ...ontrol Recommended supply power type AWZ 200 plus 7Ah battery It s possibility to set one from four identification mode Card only default mode PIN only Card or PIN Card PIN KZ 1000 IP can work in stan...

Page 4: ...85 for connection with additional modules Supply Power connectors 12V 110 mA Lock control relay output Alarm relay output Bell control output from keypad key LED located on front panel upper left Blue...

Page 5: ...m Plus TCP For additional module connection RS485 Readers and Cards Integrated reader For UNIQUE card read range 5 15 cm U For MIFARE card red range 2 5 cm M External for two way control 26 bit Wiegan...

Page 6: ...Integrated Access Controller Installation manual All rights reserved AAT HOLDING S A 6...

Page 7: ...UZ Blue Door contact SW Yellow Ground RD GND Black Exit button AN Purple PIR sensor input ALM Brown Ground RD GND GND RS485 port signal 485 Gray RS485 port signal 485 Orange 12V Red Controller supply...

Page 8: ...Integrated Access Controller Installation manual All rights reserved AAT HOLDING S A 8 Installation instruction...

Page 9: ...on is already stored card Five beeps card with this number is already added Optical indicator LED Blue LED Power on Green LED confirmation of the validity of the operation Orange LED flashing waiting...

Page 10: ...programming mode enter the code 13 then Code 00 when you want to disable the monitoring of the sensor code 01 to activate monitoring When a tamper alarm is activated an attempt to remove the unit from...

Page 11: ...lue from 00 to 99 seconds default 3 sec This is the time by which when a valid card or code is used the door will be unlocked After entering the programming mode enter the code identification mode 221...

Page 12: ...nter the PIN again Repeat the operation for subsequent reading cards with PIN codes After each added card reader generate a single beep Read the card will be cred ited automatically generated ID numbe...

Page 13: ...After adding a new administrator PIN code controller will generate a single beep and automatically exits the programming mode NOTE The default master code 000000 is mandatory to change after the firs...

Page 14: ...fault Alarm input line parameters Alarm action delay Alarm relay output 161 01 type NO 00 type NC 162 00 99 sec 0 sec default 163 1 RL1 2 RL2 3 RL1 2 4 no out Access mode setup Card only 221 Card PIN...

Page 15: ...ntroller must be installed within a protected space at a temperature of above 2 C and normal humidity Controllers in the system should be located so that the minimum distance from cables and high volt...

Page 16: ......

Reviews: