5.2.6 Setting the parameters of the alarm line 

After entering the programming mode enter the code 

161

, then 

 

Code 

01

 for NO type detector  (normally open - default setting.) 

 

Code 

00

 for NC type detector (normally closed) 

After entering the programming mode enter the code 

162

, then 

 

value from 

00

 to 

99

 seconds (default - 0 sec. default settings) 

This is the time of relay alarm action.  
Value 0 second time means “Alarm action Synchronous with input state”. 

Value from range 1 to 99 means “Alarm action delay time”. 
After entering the programming mode enter the code 

163

, then 

 

value 

1

 if the alarm siren will be activated relay 1 

 

value 

2

 when the alarm siren will be activated relay 2 

 

value 

3

 when the alarm siren will be activated relay 1 and 2 

 

value 

when none of these relays will not switch 

 

5.3 Setting the control parameters and identification mode of doors 

After entering the programming mode enter the code 

21

, then 

 

value from 

00

 to 

99

 seconds (default - 3 sec.) 

This is the time by which, when a valid card or code is used the door will be  

unlocked. 
After entering the programming mode enter the code identification mode: 

 

221

 - Card only 

 

222 

- Card + PIN 

 

223 

- PIN only 

 

224

 - Card or PIN 

 

6. User Management 

 
In standalone mode can be added up to 2000 users. Each user must be assigned 

with ID from 0000 to 1999 in the programming process and then assigned ac-
cess card number read by the reader. This allows the system administrator can 
remove the user from the database without the need a card (which can be erg. 

lost), knowing only the user's ID code. 
Cards added in standalone mode have full access to the passage (24 hours a 

day, 7 days a week). In contrast to the added cards from the program, which 
can be assigned to a limited level of access. To avoid the need for dual record 

cards and disadvantages related to the two databases cards in practice, it is rec-
ommended to use only one controller mode - standalone or network. 

Before adding users, it is recommended that the administrator has created a list 
of users with assigned four-digit ID code. This makes it easier to add new users 

later, and in particular the removal of lost cards. 

Summary of Contents for KZ-1000-IP-U

Page 1: ...Installation Manual INTEGRATED ACCESS CONTROLLER KZ 1000 IP U KZ 1000 IP M VERSION 1 0...

Page 2: ...served AAT HOLDING S A 2 1 Introduction 3 2 Controller technical data 5 3 Controller wiring diagram 6 4 Controller installation 8 5 Management in standalone mode 9 6 Programming codes table 14 7 Manag...

Page 3: ...ontrol Recommended supply power type AWZ 200 plus 7Ah battery It s possibility to set one from four identification mode Card only default mode PIN only Card or PIN Card PIN KZ 1000 IP can work in stan...

Page 4: ...85 for connection with additional modules Supply Power connectors 12V 110 mA Lock control relay output Alarm relay output Bell control output from keypad key LED located on front panel upper left Blue...

Page 5: ...m Plus TCP For additional module connection RS485 Readers and Cards Integrated reader For UNIQUE card read range 5 15 cm U For MIFARE card red range 2 5 cm M External for two way control 26 bit Wiegan...

Page 6: ...Integrated Access Controller Installation manual All rights reserved AAT HOLDING S A 6...

Page 7: ...UZ Blue Door contact SW Yellow Ground RD GND Black Exit button AN Purple PIR sensor input ALM Brown Ground RD GND GND RS485 port signal 485 Gray RS485 port signal 485 Orange 12V Red Controller supply...

Page 8: ...Integrated Access Controller Installation manual All rights reserved AAT HOLDING S A 8 Installation instruction...

Page 9: ...on is already stored card Five beeps card with this number is already added Optical indicator LED Blue LED Power on Green LED confirmation of the validity of the operation Orange LED flashing waiting...

Page 10: ...programming mode enter the code 13 then Code 00 when you want to disable the monitoring of the sensor code 01 to activate monitoring When a tamper alarm is activated an attempt to remove the unit from...

Page 11: ...lue from 00 to 99 seconds default 3 sec This is the time by which when a valid card or code is used the door will be unlocked After entering the programming mode enter the code identification mode 221...

Page 12: ...nter the PIN again Repeat the operation for subsequent reading cards with PIN codes After each added card reader generate a single beep Read the card will be cred ited automatically generated ID numbe...

Page 13: ...After adding a new administrator PIN code controller will generate a single beep and automatically exits the programming mode NOTE The default master code 000000 is mandatory to change after the firs...

Page 14: ...fault Alarm input line parameters Alarm action delay Alarm relay output 161 01 type NO 00 type NC 162 00 99 sec 0 sec default 163 1 RL1 2 RL2 3 RL1 2 4 no out Access mode setup Card only 221 Card PIN...

Page 15: ...ntroller must be installed within a protected space at a temperature of above 2 C and normal humidity Controllers in the system should be located so that the minimum distance from cables and high volt...

Page 16: ......

Reviews: