Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 75°C.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the
current
National
Electric
Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Figure 28 - Back View of Utility Entry and
Power Switch from Control Compartment
(55, 65 and 75-140 ton Units)
Note:
All units are factory wired for 208V,
230V,
380V,
460V,
or 575V.
The
transformer configuration must be checked
by a qualified technician prior to service,
especially if unit is to be connected to a 208V
or 230V
supply.
For 208V
service
interchange the yellow and red conductor on
the low voltage control transformer.
Red-Black for 208V
Yellow-Black for 230V
Wire power leads to the unit’s terminal block
or main disconnect. All wiring beyond this
point
has
been
completed
by
the
manufacturer and cannot be modified without
effecting
the
unit’s
agency/safety
certification.
Supply voltage must be within the min/max
range shown on the unit nameplate. Available
short circuit current must not exceed the short
circuit current rating (SCCR) shown on the
unit nameplate.
Utility
Entry
Summary of Contents for RN Series
Page 2: ......
Page 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Page 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Page 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Page 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Page 36: ...36 Figure 9 Steel Mounting ...
Page 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Page 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Page 129: ...Maintenance Log E Coated Coil ...