
29
Installation
AAON equipment has been designed for
quick and easy installation.
Locating Units
The curb must be mounted first and must be
located so that duct connections will be clear
of structural members of the building.
Verify rooftop or foundation can support the
total unit weight,
including
accessory
weights.
Do not position flue opening to discharge into
a fresh air intake of any other piece of
equipment. Unit must also be installed so that
the flow of combustion intake air is not
obstructed from reaching the furnace.
Vent opening must not be blocked by snow.
A minimum 12” curb must be used or the
vent outlet shall be greater than 12” off the
ground/roof.
Flue gas is dangerously hot and contains
containments. The user is responsible for
determining if vent gases may degrade
building materials.
The National Gas and Propane Installation
Code, B149.1 specifies a 6 ft. horizontal vent
terminal clearance to gas and electric meters
and relief devices.
Local codes may supersede or further place
restrictions on vent termination locations.
Table 1 - A Cabinet Unit Clearances
Location
Unit Size
6-8 and 10 tons
Front -
(Controls Side)
48”
Back - (Outside
Air)
36”
*Left Side
*6”
Right Side
48”
Top
Unobstructed
*Units with a water-cooled condenser or
chilled water coil require 48” of clearance
on the left side for service access. DX and
no cooling air handling units with an
energy recovery wheel require 24” of
clearance on the left side for service access.
Table 2 - B Cabinet Unit Clearances
Location
Unit Size
9 and 11-15 tons
Front -
(Controls Side)
48”
Back - (Outside
Air)
48”
*Left Side
*6”
Right Side
48”
Top
Unobstructed
*Units with a water-cooled condenser or
chilled water coil require 48” of clearance
on the left side for service access. DX and
no cooling air handling units with an
energy recovery wheel require 24” of
clearance on the left side for service access.
When locating gas fired units, it is
recommended the unit be installed so
that the flue discharge vents are
located at least 120 inches away from
any
opening
through
which
combustion products could enter the
building.
WARNING
Distances
from
adjacent
public
walkways,
adjacent
buildings ,
operable
windows
and
building
openings, shall conform to local codes
and/or the National Fuel Gas Code,
ANSI
Z223.1/NFPA
54, or the
National Gas & Propane Code, CSA
B149.1
WARNING
Summary of Contents for RN Series
Page 2: ......
Page 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Page 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Page 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Page 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Page 36: ...36 Figure 9 Steel Mounting ...
Page 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Page 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Page 129: ...Maintenance Log E Coated Coil ...