30
Permanent type filters may be vacuumed
and/or washed but should not be reinstalled
until thoroughly dry. Most air filters are
marked to indicate the direction of airflow,
and this should be carefully noted when they
are being installed.
The blower and motor bearings are
permanently lubricated and do not require
additional lubrication. It is recommended
that the owner have available at least one set
of replacement fuses of the size supplied
with the original equipment.
Important:
Keep coils, fans and filters
clean.
Service
In the event the unit is not functioning
correctly and a service company is required,
only a company with service technicians
qualified and experienced in both heating
and air conditioning should be permitted to
service the systems in order to keep
warranties in effect. The service tech may
call the sales representative if assistance is
required.
Replacement Parts
Parts for AAON equipment may be obtained
from your local representative. When
ordering parts, reference the unit serial
number and part number.
AAON-Longview Product Support
203 Gum Springs Road
Longview, TX 75602
Ph: 903-236-4403
Fax: 903-236-4463
www.aaon.com
Note:
Before calling, technician should have
model and serial number of the unit
available for the service department to help
answer questions regarding the unit.
General
Piping from the condensing unit to the air
handling unit is the responsibility of the
installing contractor.
Use only clean type “ACR” copper tubing
that has been joined with high temperature
brazing alloy.
The pipe sizes must be selected to meet the
actual installation conditions and not simply
based on the connection sizes at the
evaporator and/or condensing unit.
Thermal expansion valve bulbs should be
mounted with good thermal contact on a
horizontal section of the suction line close to
the evaporator, but outside the cabinet, and
well insulated.
Figure 3 - TXV Bulb Position
Hot Gas Reheat
The AAON modulating hot gas reheat
system diverts hot discharge gas from the
condenser to the air handling unit through
the hot gas line.
Field piping between the
condensing unit and the air handling unit
is required.
The line delivers the hot discharge gas to the
reheat coil and/or the hot gas bypass valve,
so it is sized as a discharge line.
Never flip a dirty filter to allow airflow
in the opposite direction.
CAUTION
Summary of Contents for F1-060
Page 31: ...31 ...
Page 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Page 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Page 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Page 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Page 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Page 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Page 45: ...45 Figure 17 5kW Electric Heat ...
Page 46: ...46 Figure 18 10 kW Electric Heat ...
Page 47: ...47 Figure 19 15 kW Electric Heat ...
Page 48: ...48 Figure 20 20 kW Electric Heat ...
Page 49: ...49 Figure 21 25 kW Electric Heat ...
Page 55: ...55 ...