
17
8.
Pull and install power wires per wiring
diagram and MCA, MOP information
herein and secure all wires firmly
9.
Replace the front control panel(s) of the
unit
FIELD INSTALLED WIRES SHOULD BE
SINGLE STRAND WIRES. USE OF
ROMEX WIRES IS NOT ACCEPTABLE.
Heating
is
accomplished
by
passing
electrical current through a specified amount
of resistance heaters, which will produce the
required heat. The indoor blower motor will
energize at the same time as the heaters.
Wiring to the air handling unit must be done
in accordance with local electrical codes
and/or standards. Check specified electrical
rating and install with proper wire sizes.
Also refer to wiring diagrams included with
the unit for wire sizes and circuit breaker
recommendations.
Field Wiring - MCA and MOP
Minimum Circuit Ampacity (MCA) and
Maximum Overcurrent Protection (MOP)
are necessary to correctly connect field
wired equipment.
The calculations for the MCA and MOP are
based on requirements of NFPA 70, the
National Electrical Code (NEC) and CSA
C22.1, the Canadian Electrical Code (CEC).
The MCA is the minimum wire size needed
to prevent the wiring from overheating
during operating conditions for the life of
the product. The MOP is the maximum
allowable circuit breaker size that will
properly disconnect power to the equipment
under anticipated fault conditions.
In the following tables, locate the kW of the
heater to be field installed, and then choose
the corresponding MCA and MOP values to
correctly size the wire gauge(s) and circuit
breaker(s), respectively.
Table 1 - Electric Heat Minimum Circuit
Ampacity
230V 208V
Line
1
Line
2
Line
3
kW
kW
MCA MCA MCA
5
3.75
26.0
10
7.50
52.1
15
11.25
52.1
26.0
20
15.00
52.1
52.1
25
18.75
52.1
52.1
26.0
Overcurrent protection less than that
recommended on the unit's "Specification
Sheet" could result in unnecessary fuse
failure and service call. The manufacturer
bears no responsibility for damage caused to
the equipment as a result of not using the
recommended size for the protective devices
as listed on the unit's rating plate.
Table 2 - Electric Heat Maximum
Overcurrent Protection
230V 208V
Line
1
Line
2
Line
3
kW
kW
MOP
MOP
MOP
5
3.75
30
10
7.50
60
15
11.25
60
30
20
15.00
60
60
25
18.75
60
60
30
Heat Pump
For heat pump equipped split system
configurations, the heat pump is the primary
heat source during a call for heat. During
operation at low ambient temperatures
where the heat pump alone cannot satisfy
the space temperature set point, electric
resistance heat elements are activated.
Below about 17°F, only the electric heat is
operable; the heat pump is not active.
Summary of Contents for F1-060
Page 31: ...31 ...
Page 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Page 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Page 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Page 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Page 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Page 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Page 45: ...45 Figure 17 5kW Electric Heat ...
Page 46: ...46 Figure 18 10 kW Electric Heat ...
Page 47: ...47 Figure 19 15 kW Electric Heat ...
Page 48: ...48 Figure 20 20 kW Electric Heat ...
Page 49: ...49 Figure 21 25 kW Electric Heat ...
Page 55: ...55 ...