
23
Checking Liquid Sub-cooling
1.
Measure the temperature of the
liquid
line
as it leaves the condenser coil.
2.
Read the gauge pressure reading of the
liquid line
close to the point where the
temperature was taken. You must use liquid
line pressure, as it will vary from discharge
pressure due to condenser coil pressure
drop.
3.
Convert the pressure obtained in Step 2 to
a
saturated
temperature
using
the
appropriate refrigerant temperature-pressure
chart.
4.
Subtract the measured liquid line
temperature in Step 1 from the saturated
temperature in Step 3 to determine the liquid
sub-cooling.
5.
Compare calculated sub-cooling to
TABLE 7 for the appropriate unit type and
options.
Checking Evaporator Superheat
1.
Measure the temperature of the
suction
line
close to the compressor.
2.
Read gauge pressure at the
suction line
close to the compressor.
3.
Convert the pressure obtained in Step 2 to
a
saturated
temperature
using
the
appropriate refrigerant temperature-pressure
chart.
4.
Subtract the saturated temperature in Step
3
from
the
measured
suction
line
temperature in Step 1 to determine the
evaporator superheat.
5.
Compare calculated superheat to TABLE
7 for the appropriate unit type and options.
Adjusting Sub-cooling and Superheat
Temperatures
The system is
overcharged
if:
1.
the sub-cooling temperature is too high
and
2.
the evaporator is fully loaded (low loads
on the evaporator result in increased sub-
cooling)
and
3.
the evaporator superheat is within the
temperature range as shown in Table 7 (high
superheat results in increased sub-cooling)
Table 7 - Acceptable Refrigeration Circuit
Values
Air-Cooled Cond./Air-Source Heat Pump
Sub-Cooling**
8-15°F / 2-4°F (HP)*
Sub-Cooling with
Hot Gas Reheat**
8-15°F / 2-6°F (HP)*
Superheat***
8-15°F
*In cooling mode operation
**Sub-cooling must be increased by 2°F per
20 feet of vertical liquid line rise for R-410A
***Superheat will increase with long
suction line runs.
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
The system is
undercharged
if:
1.
The superheat is too high
and
2.
The sub-cooling is too low.
DO NOT OVERCHARGE!
Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
CAUTION
Summary of Contents for F1-060
Page 31: ...31 ...
Page 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Page 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Page 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Page 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Page 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Page 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Page 45: ...45 Figure 17 5kW Electric Heat ...
Page 46: ...46 Figure 18 10 kW Electric Heat ...
Page 47: ...47 Figure 19 15 kW Electric Heat ...
Page 48: ...48 Figure 20 20 kW Electric Heat ...
Page 49: ...49 Figure 21 25 kW Electric Heat ...
Page 55: ...55 ...