24
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.
Elevation Limitations
See CB Series Installation, Operation, and
Maintenance manual for rise and run
limitations. All lengths listed are in
equivalent feet. An equivalent foot of the
line includes the pressure drop of all valves,
components, fittings and other pipes in the
sections.
Evaporator Coil
The indoor coil is pressurized. The copper
caps must be punctured to permit a gradual
escape of the pressure prior to unsweating
those caps. Immediately couple the tubing to
the indoor unit to avoid exposing the coils to
moisture. A properly sized filter drier is
furnished in the condenser. When making
solder connections, make sure dry nitrogen
flows through the lines, when heating the
copper, to prevent oxidization inside of the
copper.
Evaporator coils are shipped under
high pressure. Use extreme care and
follow the installation instructions
provided with the evaporator coil to
avoid personal injury.
CAUTION
Summary of Contents for F1-060
Page 31: ...31 ...
Page 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Page 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Page 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Page 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Page 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Page 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Page 45: ...45 Figure 17 5kW Electric Heat ...
Page 46: ...46 Figure 18 10 kW Electric Heat ...
Page 47: ...47 Figure 19 15 kW Electric Heat ...
Page 48: ...48 Figure 20 20 kW Electric Heat ...
Page 49: ...49 Figure 21 25 kW Electric Heat ...
Page 55: ...55 ...