is
Explanation of type of appliance
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
3.10.3
Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Flue gas discharge requirements for concentric systems (C13, C33)
Caution
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe
length may
not
be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum
number of bends may
not
be exceeded.
The following example illustrates how to use the table.
Type of appliance
Description
B23
Air for combustion is drawn from the boiler room.
C13
Concentric and / or parallel wall flue terminal
C33
Concentric and / or parallel roof flue terminal
C43
Appliances on common air supply and flue gas discharge (concentric and / or
parallel) in multi-storey building.
C53
Air supply and flue terminal types mixed.
C63
Appliances supplied without flue components and / or terminal. These
appliances must be installed in compliance with local regulations.
Appliance
Diameter
Maximum length Maximum
number of 90°
bends
SGS 80
130/200mm
15m
3
SGS 100
130/200mm
15m
3
Summary of Contents for SGS - 100
Page 1: ...80 100 Installation User and Service Manual Installation User and Service Manual...
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual SGS gis...
Page 8: ...Table of contents 8 Instruction manual SGS...
Page 12: ...Introduction 12 Instruction manual SGS 1 gis...
Page 44: ...Installation 44 Instruction manual SGS 3 is...
Page 62: ...Shutting down 62 Instruction manual SGS 10 gis...
Page 92: ...Maintenance frequency 92 Instruction manual SGS 14 is...
Page 101: ...Instruction manual SGS 101 is...
Page 106: ...Appendices 106 Instruction manual SGS 17 is...