Gas data
Gas data
Description II
2H3+
Unit
SGS 80
SGS 100
Natural gas
Gas category G20-20 mbar
Orifice diameter
mm
6.30
6.80
Nominal load (gross calorific value)
kW
86.6
105.5
Nominal output
kW
81.9
99.8
Supply pressure
mbar
20
20
Burner pressure
mbar
7.0
6.0
Gas consumption
(*)
m
3
/h
8.3
10.1
LP gas
Gas category G31-37mbar (propane)
Orifice diameter
mm
4.70
5.10
Nominal load (gross calorific value)
kW
84.8
103.3
Nominal output
kW
81.9
99.8
Supply pressure
mbar
37
37
Burner pressure
(†)
mbar
13
13
Gas consumption
(*)
kg/h
6.1
7.4
(*) Based on 1013.25 mbar and 15 °C.