is
Instruction manual BFC
68
13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Cause
Solution
Remark
Gas smell
Gas leak
Warning
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Contact your installation engineer or local gas company
immediately.
Display is off
Appliance is turned off
Start the appliance up
(9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the BFC electrical diagram
(17 "Appendices")
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.
Summary of Contents for cyclone BFC - 80
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual BFC gis...
Page 8: ...Table of contents 8 Instruction manual BFC...
Page 12: ...Introduction 12 Instruction manual BFC 1 gis...
Page 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Page 46: ...Draining 46 Instruction manual BFC 6 gis...
Page 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Page 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Page 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Page 92: ...Appendices 92 Instruction manual BFC 17 is...
Page 94: ...Instruction manual BFC 94...