Installation
28
Instruction manual BFC
3
is
Explanation of type of appliance
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
3.9.3
Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Flue gas discharge requirements for concentric systems (C13, C33)
Caution
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe
length may
not
be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum
number of bends may
not
be exceeded.
The following example illustrates how to use the table.
Practical example of concentric flue gas discharge
Example
The figure shows a BFC 100 installation. The appliance must be fitted with 12m
of concentric pipe (C13/C33) and three 90 degree bends. We need to check
whether this configuration complies with the requirements stated in the table.
Type of appliance
Description
B23
Air for combustion is drawn from the boiler room.
C13
Concentric and / or parallel wall flue terminal
C33
Concentric and / or parallel roof flue terminal
C43
Appliances on common air supply and flue gas discharge (concentric and / or
parallel) in multi-storey building.
C53
Air supply and flue terminal types mixed.
C63
Appliances supplied without flue components and / or terminal. These
appliances must be installed in compliance with local regulations.
Appliance
Diameter
Maximum length Maximum
number of 90°
bends
BFC 80
130/200mm
15m
3
BFC 100
130/200mm
15m
3
Summary of Contents for cyclone BFC - 80
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual BFC gis...
Page 8: ...Table of contents 8 Instruction manual BFC...
Page 12: ...Introduction 12 Instruction manual BFC 1 gis...
Page 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Page 46: ...Draining 46 Instruction manual BFC 6 gis...
Page 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Page 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Page 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Page 92: ...Appendices 92 Instruction manual BFC 17 is...
Page 94: ...Instruction manual BFC 94...