Installation
24
Instruction manual BFC
3
is
3.6
Water connections,
Vented
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations
(1.3 "Regulations")
.
3.6.1
Cold water side
See (A) in the installation diagram
(3.5 "Installation diagram")
.
1. Fit an approved stop valve (4) on the cold water side between the cold water
head tank (18) and the appliance, as required by
regulations
(1.3 "Regulations")
.
3.6.2
Hot water side
See (B) in the installation diagram
(3.5 "Installation diagram")
.
Note
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve (3).
2. Optional: fit a temperature gauge (12) so you can check the temperature of
the tap water.
3. Fit a stop valve (4) in the hot water outlet pipe, for use when servicing.
4. If a circulation pipe is required, continue further by installing the circulation
pipe
(3.6.3 "Circulation pipe")
.
3.6.3
Circulation pipe
See (C) in the installation diagram
(3.5 "Installation diagram")
.
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the cold water supply pipe.
3.6.4
Condensation drainage
1. Fit a sloping wastewater pipe to the siphon (13) for condensation drainage
and connect this to the wastewater discharge in the boiler room.
Caution
All fittings behind the siphon must be condensation-resistant.
Summary of Contents for cyclone BFC - 80
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual BFC gis...
Page 8: ...Table of contents 8 Instruction manual BFC...
Page 12: ...Introduction 12 Instruction manual BFC 1 gis...
Page 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Page 46: ...Draining 46 Instruction manual BFC 6 gis...
Page 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Page 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Page 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Page 92: ...Appendices 92 Instruction manual BFC 17 is...
Page 94: ...Instruction manual BFC 94...