Gas data
Gas data
Description II
2H3P
Unit
BFC 80
BFC 100
Natural gas
Gas category G20-20 mbar
Orifice diameter
mm
6.30
6.80
Nominal load (gross calorific value)
kW
86.6
105.5
Nominal output
kW
81.9
99.8
Supply pressure
mbar
20
20
Burner pressure
mbar
7.0
6.0
Gas consumption
(*)
m
3
/h
8.3
10.1
LP gas
Gas category G31-37mbar (propane)
Orifice diameter
mm
4.70
5.10
Nominal load (gross calorific value)
kW
84.8
103.3
Nominal output
kW
81.9
99.8
Supply pressure
mbar
37
37
Burner pressure
(†)
mbar
13
13
Gas consumption
(*)
kg/h
6.1
7.4
(*) Based on 1013.25 mbar and 15 °C.
(†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to
the supply pressure. In practice, however, the burner pressure will be lower.
Summary of Contents for cyclone BFC - 80
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual BFC gis...
Page 8: ...Table of contents 8 Instruction manual BFC...
Page 12: ...Introduction 12 Instruction manual BFC 1 gis...
Page 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Page 46: ...Draining 46 Instruction manual BFC 6 gis...
Page 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Page 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Page 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Page 92: ...Appendices 92 Instruction manual BFC 17 is...
Page 94: ...Instruction manual BFC 94...