Appliance with concentric flue gas discharge material
According to the table, the maximum length allowed is 15 metres, and there may
be up to three 90° bends. Both requirements are fulfilled.
Specifications
Caution
For type C13 and C33 installations,A.O. Smith prescribes the use of a roof
or wall-mounted terminal, exclusively of a type approved for the appliance. Use
of an incorrect roof or wall-mounted flue terminal can cause the installation to
malfunction.
IMD-0286 R2