Installation
32
Instruction manual BFC
3
is
Concentric roof flue terminal specifications C33
3.9.4
Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre towards
the water heater.
Chimney flue requirements for parallel systems
You must use the longest pipe when calculating the pipe length. For example, if
the chimney pipe is 10 metres and the air supply pipe is 8 metres, use 10 metres
as the length for the calculation. Next, add the L
equivalent
for
every
90° and 45°
bend to this 10 metres, in
both
the air supply and flue gas outlet. The following
practical example illustrates how to use the table.
Subject
Description
Roof conduit set:
•
1x roof conduit
(incl. clamping
ring)
•
1x
p
ipe 1000 mm
•
1x adhesive sheet
Art. No.
BFC 28, 30, 50, 60
0304 423
1
BFC 80, 100, 120
0306 855
1
Manufacturer
Muelink & Grol
Type
M2000 DDV HR-C
Pipe material
Construction
Concentric
Flue gas discharge
Thick-walled aluminium with lipped sealing ring.
Air supply
Thin-walled galvanised sheet steel.
Pipe diameters
Flue gas discharge
BFC 28, 30, 50, 60
Ø 100 mm
BFC 80, 100, 120
Ø 130mm
Air supply
BFC 28, 30, 50, 60
Ø 150 mm
BFC 80, 100, 120
Ø 200 mm
(1)
No other roof flue terminal may be used. Use this item number to order the roof flue terminal set from the
supplier
, manufacturer or wholesalor.
Appliance
Diameter
1
Maximum
total
length
L
equivalent
90
o
bend
L
equivalent
45
o
bend
BFC 28, 30, 50, 60
100 mm
55 m
4.6 m
1.2 m
BFC 80, 100, 120
130 mm
65 m
2.4 m
1.4 m
BFC 28, 30, 50, 60
130 mm
100 m
2.4 m
1.4 m
BFC 80, 100, 120
150 mm
100 m
2.6 m
1.6 m
1) Parallel systems with diameter of 100 mm or 130 mm. If the maximum total
length when using diameter 100 mm is insufficient, diameter 130 mm should
be used. If the maximum total length when using diameter 130 mm is
insufficient, diameter 150 mm should be used. Any diameter enlargement
must be carried out on both air supply and flue gas outlet.
Summary of Contents for Cyclone BFC-28
Page 4: ...E2...
Page 6: ...4 Instruction manual BFC gis...
Page 10: ...Contents 8 Instruction manual BFC...
Page 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33...
Page 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is...
Page 58: ...Status of the water heater 56 Instruction manual BFC 8 gis...
Page 62: ...Shutting down 60 Instruction manual BFC 10 gis...
Page 74: ...Service program 72 Instruction manual BFC 12 is...
Page 88: ...Service interval 86 Instruction manual BFC 14 is...
Page 97: ...Instruction manual BFC 95 is...
Page 102: ...Instruction manual BFC 100...