Instruction manual BFC
81
F06 (blocking error)
Short circuit between
flame probe and earth
Damaged cable in
contact with metal
surface or bent flame
probe.
Check the wiring and the flame probe. Replace the wiring and/or
flame probe if necessary.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Ceramic part of the
flame probe is
broken/cracked.
1. Check whether the ceramic part of the flame probe is still intact,
in the vicinity of the air distribution plate of the burner.
2. If not the flame probe must be replaced.
F07 (lock out error)
A flame has been
detected after the gas
control valve was
closed.
Defective gas control
valves
1. Check whether there is still burner pressure present, after the
gas control valves have closed.
2. Check whether a flame is still present, after the gas control
valves have closed.
3. If this is the case, the gas control valve must be replaced.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F08 (lock out error)
Error message from
safety relay
Flame detection before
the gas control valve
opened.
1. Reset controller.
2. If the error appears again, replace the controller.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F09 (lock out error)
Water temperature
protection.
Temperature at the top
of the tank exceeds
93
o
C.
1. Check that the circulation pump (if present) is working
2. Check the position of temperature sensor T
1
3. Reset controller
If the error cannot be resolved or is persistent, contact your
installation engineer
F11 (blocking error)
Flame detection with
closed gas control
valve.
Defective gas control
valves
See F07.
F19 (blocking error)
Power supply voltage is
too low.
There is not enough
supply voltage.
1. Check that there is power to the controller
2. The measured voltage must be 230 V
AC
(-15%, +10%)
See the electrical diagram (17 "Appendices").
If the error persists, consult your installation engineer
Code + description
Cause
Measure
Remark
Summary of Contents for Cyclone BFC-28
Page 4: ...E2...
Page 6: ...4 Instruction manual BFC gis...
Page 10: ...Contents 8 Instruction manual BFC...
Page 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33...
Page 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is...
Page 58: ...Status of the water heater 56 Instruction manual BFC 8 gis...
Page 62: ...Shutting down 60 Instruction manual BFC 10 gis...
Page 74: ...Service program 72 Instruction manual BFC 12 is...
Page 88: ...Service interval 86 Instruction manual BFC 14 is...
Page 97: ...Instruction manual BFC 95 is...
Page 102: ...Instruction manual BFC 100...